Analog Value Representation for Themocouple Type B

Table 5-22 Analog Value Representation for Thermocouple Type B

Type B

Units

Type B

Units

Type B

Units

Type B

in

5

C

Deci-

mal

Hexa-

deci-

mal

Type B

in

5

F

Deci-

mal

Hexa-

deci-

mal

Type B

in K

Deci-

mal

Hexa-

deci-

mal

Range

> 2070.0

32767

7FFF

H

> 3276.6

32767

7FFF

H

> 2343.2

32767

7FFF

H

Overflow

2070.0

:

1821.0

20700

:

18210

50DC

H

:

4722

H

3276.6

:

2786.6

32766

:

27866

7FFE

H

:

6CDA

H

2343.2

:

2094.2

23432

:

20942

5B88

H

:

51CE

H

Overrange

1820.0

:

0,0

18200

:

0

4718

H

:

0000

H

2786.5

:

–32.0

27865

:

–320

6CD9

H

:

FEC0

H

2093.2

:

273.2

20932

:

2732

51C4

H

:

0AAC

H

Rated range

:

–120.0

:

–1200

:

FB50

H

:

–184.0

:

–1840

:

F8D0

H

:

153.2

:

1532

:

05FC

H

Underrange

< –120.0

–32768

8000

H

< –184.0

–32768

8000

H

< 153.2

32768

8000

H

Underflow

Analog Value Representation for Thermocouple Type E

Table 5-23 Analog Value Representation for Thermocouple Type E

Type E

Units

Type E

Units

Type E

Units

Type E

in

5

C

Deci-

mal

Hexade-

cimal

Type E

in

5

F

Deci-

mal

Hexa-

deci-

mal

Type E

in K

Deci-

mal

Hexa-

deci-

mal

Range

> 1200.0

32767

7FFF

H

> 2192,0

32767

7FFF

H

> 1473.2

32767

7FFF

H

Overflow

1200.0

:

1000.1

12000

:

10001

2EE0

H

:

2711

H

2192.0

:

1833.8

21920

:

18338

55A0

H

:

47A2

H

1473.2

:

1274.2

14732

:

12742

398C

H

:

31C6

H

Overrange

1000.0

:

–270.0

10000

:

–2700

2710

H

:

F574

H

1832.0

:

–454.0

18320

:

–4540

4790

H

:

EE44

H

1273.2

:

0

12732

:

0

31BC

H

:

0000

H

Rated range

< –270.0

<
–2700

< F574

H

< –454.0

<
–4540

<EE44

H

< 0

< 0

<0000

H

Underflow

In the case of incorrect wiring (for example, polarity reversal or open inputs) or of a sensor error in the
negative range (for example, incorrect thermocouple type), the analog input module reports an
underflow...

...if F0C4

H

is violated and

outputs 8000

H

...if FB70

H

is violated and

outputs 8000

H

...if E5D4

H

is violated and

outputs 8000

H