Technical specifications – Siemens Simatic S7-400 User Manual

Page 203

Advertising
background image

Digital Modules

4-81

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications

of the SM 422; DO 8

120/230 VAC/5 A

Programming package

Associated programming
package

As of STEP 7 V 2.0

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 800 g

Data for Specific Module

Number of outputs

8

Length of cable

•

Unshielded

•

Shielded

600 m

1000 m

Voltages, Currents, Potentials

Rated load voltage L1

Permitted frequency range

79 to 264 VAC

47 to 63 Hz

Total current of the outputs

Up to 40

_

C

Up to 60

_

C

With fan subassembly

Max. 16 A

24 A

Max. 8 A

20 A

Isolation

•

Between channels and
backplane bus

Yes

•

Between the channels

In groups of

Yes

1

Permitted potential difference

•

Between the outputs of the
different groups

500 VAC

Insulation resistance

4000 VAC

Current consumption

•

From the backplane bus

•

From load voltage L +
(without load)

Max. 250 mA

Max. 1.5 mA

Power dissipation of the
module

Typ. 16 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

None

Diagnostic functions

Parameters cannot be
assigned

•

Group error display

–

For internal fault

Red LED (INTF)
failed fuse

–

For external fault

Red LED (EXTF)
failed load voltage

Data for Selecting an Actuator

Output voltage

•

At signal “1”

At maximum current
min. L1 (–1.5 Vrms)

At maximum current
min. L1 (–10.7 Vrms)

Output current

•

At signal “1”

Rated value

5 A

Permitted range

10 mA to 5 A

Permitted surge current
(per group)

Max. 50 A per cycle

•

At signal “0” (leakage
current)

Max. 3.5 mA

Output delay (for resistive load)

•

From “ 0” to “1”

Not more than 1 AC
scan cycle

•

At “1” to “0”

Not more than 1 AC
scan cycle

Minimum load current

10 mA

Zero cross inhibit voltage

Max. 55 V

Size of the motor starter

Max. size 5 to NEMA

Lamp load

Max. 100 W

Parallel connection of 2
outputs

•

For redundant triggering of
a load

Possible (only outputs
connected to the same
load)

Triggering a digital input

Possible

Switch rate

•

For resistive load

Max. 10 Hz

•

For inductive load
to IEC 947-5-1, DC 13

Max. 0.5 Hz

•

For lamp load

1 Hz

Short-circuit protection of the
output

Fuse, 8 A, 250 V (per
output)

•

Min. current required for
fuse to blow

Min. 100 A

•

Max. response time

Max. 100 ms

Replacement fuses

•

Wickmann

•

Schurter

•

Littelfuse

Fuse, 8 A, quick-acting

194-1800-0

SP001.1013

217.008

Advertising
This manual is related to the following products: