10 Engineering Information

Issue 03/01

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

128

6SE6400-5CA00-0BP0

10.2.4 PI

Output

Limits

The PI controller generates the frequency at which the inverter runs. This is
generated as a % which is normalized into Hz via P2000. The user can limit the
output range of the controller using parameters P2291 and P2292. While the
inverter will only operate within the frequency range defined by F

min

(P1080) and

F

max

(P1082), the PI output limits can be used to further limit the output frequency.

Once one of the limits has been reached a bit is set (P0053.A or P0053.B) which
can be connected to the digital output via P0731, or used for internal control
purposes using BiCo.

NOTE:
If F

max

(P1082) is greater than the value in P2000, then either P2000 or P2291

should be adjusted to allow F

max

to be reached.

Setting P2292 to a negative value allows bipolar operation of the PI controller.

10.2.5 Further

features

Further features, such as a PI setpoint trim can be accessed in user access level 3
(P0003 = 3). These features are described in the Parameter List.

PID

MOP

ADC

PID

SUM

PID

PID

FF

USS

BOP link

USS

COM link

CB

COM link

ADC2

P2254

P2253

PID

RFG

PID

PT1

0

1

− ∆

PID

P2200

P2253

PID

PT1

PID

SCL

Output

PID

Motor

control

Figure 10-10 PI Basic Block Diagram