4 tightening torque for fixing screws – Siemens MICROMASTER 411 User Manual

Page 96

Advertising
background image

7 Specifications

Issue 03/01

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

96

6SE6400-5CA00-0BP0

7.3

Tightening Torque, Cable cross sections for Power
Supply and Motor Terminals

Table 7-4

Power Supply & Motor Terminal Wire Sizes/Tightening Torques

Terminals

Units of

measurement

Case Size B

Case Size C

[Nm] 1,3 1,3

Terminal Tightening Torque

[lbf.in] 12

12

[mm

2

] 1,5

2,5

Minimum Cable Cross Section

[AWG] 16

14

[mm

2

] 4

4

Maximum Cable Cross Section

[AWG] 12

12

7.4

Tightening Torque for Fixing Screws

Table 7-5

Fixing Screw Recommended Tightening Torque

Description

Units of

measurement

Case Size B

Case Size C

[Nm]

2,5 (M5) 2,5 (M5)

Inverter Cover Screws

[lbf.in]

21,3 (M5) 21,3 (M5)

[Nm]

0,8 (M3) 0,8 (M3)

Filter Board Retention Screws

[lbf.in]

7,0 (M3) 7,0 (M3)

[Nm]

0,8 (M3) 0,8 (M3)

I/O Board Retention Screws

[lbf.in]

7,0 (M3) 7,0 (M3)

[Nm] 1,5/2,5

M4/M5

2,5

(M5)

Terminal Housing to Motor Fixing
Screws

[lbf.in] 10,6/21,3

M4/M5

21,3 (M5)

Advertising