Flow chart quick commissioning (level 1 only) – Siemens MICROMASTER 411 User Manual

Page 54

Advertising
background image

3 Commissioning

Issue 03/01

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

54

6SE6400-5CA00-0BP0

Flow chart Quick Commissioning (Level 1 Only)








































1) related parameters – please refer to motor rating plate drawing.
2) Denotes parameters that contain more detailed lists of possible settings for use in specific

applications. Please refer to the Parameter List.

P0010

Start Quick Commissioning

0 Ready to Run
1 Quick

Commissioning

30 Factory Setting
Note
P0010 must always be set back to '0' before
operating the motor. However if P3900 = 1 is set
after commissioning this is done automatically.

P0100 Operation for Europe/N. America
0 Power in kW; f default 50 Hz
1

Power in hp; f default 60 Hz

2 Power in kW; f default 60 Hz
Note
Settings 0 & 1 can be changed using the 60Hz
Jumper to allow permanent setting.

P0305 Rated Motor Current1)
0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate

P0307 Rated Motor Power1)
0 kW - 2000 kW
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp

P0310 Rated Motor Frequency1)
12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate

P0311 Rated Motor Speed1)
0 - 40000 1/min
Nominal motor speed (rpm) from rating plate

P0700 Selection of Command Source 2)
(on / off / reverse)
0 Factory

Setting

1 Basic Operator Panel
2 Terminal / Digital Inputs (Default)

P1000 Selection of Frequency Setpoint 2)
0 No frequency setpoint
1. BOP frequency control

↑↓

2. Analogue

Setpoint

27.

Setpoint Addition: Analogue Setpoint &

Control Potentiometer(Default)

P1080 Min. Motor Frequency
Sets minimum motor frequency (0-650Hz) at which
the motor will run irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.

P1082 Max. Motor Frequency
Sets maximum motor frequency (0-650Hz) at which
the motor will run at irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.

P1120 Ramp-Up Time
0 s - 650 s
Time taken for the motor to accelerate from
standstill up to maximum motor frequency.

P1121 Ramp-Down Time
0 s - 650 s
Time taken for motor to decelerate from maximum
motor frequency down to standstill.

P3900 End Quick Commissioning
0 No Quick Commissioning.
1 Perform Quick Commissioning with factory reset

of all other Parameters (Recommended).

P0304 Rated Motor Voltage1)
10 V - 2000 V
Nominal motor voltage (V) from rating plate

Advertising