3 Commissioning

Issue 03/01

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

50

6SE6400-5CA00-0BP0

3.3.4.1 Commissioning

with

the

Basic Operator Panel (BOP)

The Basic Operator Panel (BOP), which is available as an
optional accessory, provides the user with access to the
inverter parameters and enables you to customize the
settings of your COMBIMASTER 411 & MICROMASTER
411. The BOP is mounted in an Operator Panel Mounting
Kit and connected to the COMBIMASTER 411 &
MICROMASTER 411 via the serial interface (see Figure
3-9). The BOP can be used to configure several
COMBIMASTER 411 & MICROMASTER 411 Inverters.

The BOP features a five-digit, seven-segment display for

showing parameter numbers and values, alarm and fault messages and setpoints
and actual values. Parameter sets cannot be saved via the BOP.

Control functions for the inverter (ON/OFF,

,

, reverse) are not active in the

works settings. In order to specify this command via the BOP, P0700 = 1 must be
set.

If the BOP connection is removed during normal running the drives is stopped and
the motor coasts to standstill.

Table 3-5 shows the factory default settings for operation via the BOP.

Table 3-5

Default Settings for BOP Operation

Parameter Meaning

Default

Europe

(North

America)

P0100

Operating Mode Europe/US

50 Hz, kW (60 Hz, hp)

P0307

Power (rated motor)

kW (Hp)

P0310

Motor frequency rating

50 Hz (60 Hz)

P0311

Motor speed rating

1395 (1680) rpm [depending on variant]]

P1082

Maximum Motor Frequency

50 Hz (60 Hz)