6 Troubleshooting

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

85

No setpoint values from CB (communication board) during telegram off time

Diagnose & Remedy

Check CB and communication partner

F0071 USS (BOP-link) setpoint fault

OFF2

Possible Causes

No setpoint values from USS during telegram off time

Diagnose & Remedy

Check USS master

F0072 USS (COMM link) setpoint fault

OFF2

Possible Causes

No setpoint values from USS during telegram off time

Diagnose & Remedy

Check USS master

F0080 ADC lost input signal

OFF2

Possible Causes

Broken wire

Signal out of limits

F0085 External

Fault

OFF2

Possible Causes

External fault triggered via for example terminal inputs

Diagnose & Remedy

Disable for example terminal input for fault trigger

F0090 Encoder feedback loss

OFF2

Possible Causes

Signal from Encoder lost

Diagnose & Remedy

Check encoder fitted. If encoder not fitted, set P0400 = 0 and select SLVC mode (P1300 = 20 or 22)

If encoder fitted, check correct encoder selected (check encoder set-up in P0400).

Check connections between encoder and inverter

Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in
r0061)

Increase encoder loss threshold in P0492

F0101 Stack

Overflow

OFF2

Possible Causes

Software error or processor failure

Diagnose & Remedy

Run self test routines

F0221 PID Feedback below min. value

OFF2

Possible Causes

PID Feedback below min. value P2268

Diagnose & Remedy

Change value of P2268

Adjust feedback gain

F0222 PID Feedback above max. value

OFF2

Possible Causes

PID feedback above max. value P2267

Diagnose & Remedy

Advertising