10 Engineering Information

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

147

10.12

Shock and Vibration

The inverter has been tested for compliance with the following standards.

10.12.1 Vibration

Stress during Operation (Single Sine Sweep)

Required Standards:

EN 60721-3-3 class 3M6 and 3M8

Test standards:

EN60068-2-6, test Fc

Case Size B:

Class 3M6: 10-58 Hz/ 0.15 mm, 58-200 Hz/ 2g

Case Size C:

Class 3M6: 10-58 Hz/ 0.15 mm, 58-200 Hz/ 2g

10.12.2 Shock Stress during Operation (Half Sine Shock)

Required Standards:

EN 60721-3-3

Test standards:

EN 60068-2-27, test Ea

Case Size B:

Peak acceleration 5g - duration of shock 30 ms

Case Size C:

Peak acceleration 5g - duration of shock 30 ms

10.12.3 Vibration

and

Shock stress during Transport

Required Standards:

EN 60721-3-3

Test standards:

EN 60068-2-27, Test Ea

Class 2M2:

5-9 Hz/ 3.5 mm, 9-200 Hz/ 1g

Class 2M1:

Peak acceleration 15g - duration of shock 11 ms.

The inverter meets class 2M2 for Vibration stress and 2M1 for shock stress in
product packaging.