1 ramp times using jumpers – Siemens MICROMASTER 411 User Manual

Page 46

Advertising
background image

3 Commissioning

Issue 03/01

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

46

6SE6400-5CA00-0BP0

3.3.1

Ramp Times Using Jumpers

Inverter ramp times are set using a series of 5 jumpers (fit jumper to enable
function). Each jumper must be set as shown in Table 3-1.

The jumpers overwrite the default settings or the ramp times specified using
BOP/AOP/IBN software.

The inverter recognizes when jumper values have been set when power is re-
applied.

CAUTION
Jumpers have priority in setting ramp times. When the jumpers are removed the
ramp times are not changed. It is then possible to change ramp times via the
parameters (using the BOP).

Ramp times apply to Ramp Up and Ramp Down. Jumper locations are as shown in
Figure 3-3.

Figure 3-3

Ramp Time Jumpers

Using up to 5 jumpers allows ramp times to be set between 1 - 240 s. Also see
Table 3-1.

Table 3-1

Ramp Time Adjustment Jumpers

Time [s] X20 X10 5 s 2 s 1 s

Time [s] X20 X10 5 s 2 s 1 s

1

Ч

70

Ч

Ч

Ч

2

Ч

80

Ч

Ч

Ч

Ч

3

Ч

Ч

90

Ч

Ч

Ч

Ч

5

Ч

100

Ч

Ч

6

Ч

Ч

120

Ч

Ч

Ч

7

Ч

Ч

140

Ч

Ч

Ч

8

Ч

Ч

Ч

150

Ч

Ч

Ч

10

Ч

Ч

160

Ч

Ч

Ч

Ч

20

Ч

Ч

180

Ч

Ч

Ч

Ч

30

Ч

Ч

Ч

210

Ч

Ч

Ч

Ч

50

Ч

Ч

240

Ч

Ч

Ч

Ч

Ч

60

Ч

Ч

Ч

Advertising