Siemens MICROMASTER 411 User Manual

Page 86

Advertising
background image

6 Troubleshooting

Issue 03/01

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

86

6SE6400-5CA00-0BP0

Change value of P2267

Adjust feedback gain

F0450 BIST Tests Failure

OFF2

Possible Causes

Fault value = 1: Some power section tests have failed

2: Some control board tests have failed

4: Some functional tests have failed

8: Some IO board tests have failed (MM 420 only)

16: Internal RAM failed on power-up check

Diagnose & Remedy

Hardware defect, contact Customer Support / Service Department

F0452 Belt Failure Detected

OFF2

Possible Causes

Load conditions on motor indicate belt failure or mechanical fault.

Diagnose & Remedy

Check the following:

No breakage, seizure or obstruction of drive train.

If using an external speed sensor, check for correct function. Check parameters:
P2192 (delay time for permitted deviation)

If using the torque envelope, check parameters:
P2182 (threshold frequency f1)
P2183 (threshold frequency f2)
P2184 (threshold frequency f3)
P2185 (upper torque threshold 1)
P2186 (lower torque threshold 1)
P2187 (upper torque threshold 2)
P2188 (lower torque threshold 2)
P2189 (upper torque threshold 3
P2190 (lower torque threshold 3)
P2192 (delay time for permitted deviation)

Advertising