background image

Issue 03/01

3 Commissioning

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

55

Motor data for parameterization

Figure 3-7

Typical Motor Rating Plate Example

NOTICE

P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters is
shown depending on the settings of P0100.

Changing motor parameters is not possible unless P0010 = 1(factory setting)
and P0004 = 0 or 3.

Ensure that the inverter is configured correctly to the motor.

3.3.4.4

Reset to Factory default

To reset all parameters to the factory default settings; the following parameters
should be set as follows:
1. Set P0010 = 30
2. Set P0970 = 1

NOTICE
1. The reset process can take up to 3 minutes to complete.
2. Refer to Parameter P0399 for description on saving motor data sets while

performing a reset to the factory defaults.