2 alarm messages, A0501 current limit, A0502 overvoltage limit – Siemens MICROMASTER 411 User Manual

Page 87: A0503 undervoltage limit, A0504 inverter overtemperature, A0505 inverter i

Advertising
background image

Issue 03/01

6 Troubleshooting

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

87

6.3.2 Alarm

Messages

Alarm messages are stored in parameter r2110 under their code number (e.g.
A0503 = 503) and can be read out from there.

A0501 Current

Limit

Possible Causes

Motor power (P0307) does not correspond to the inverter power (P0206)

Motor leads are too long

Earth faults

Diagnose & Remedy

Check the following:

Motor power (P0307) must correspond to inverter power (r0206)

Cable length limits must not be exceeded

Motor cable and motor must have no short-circuits or earth faults

Motor parameters must match the motor in use

Value of stator resistance (P0350) must be correct

Motor must not be obstructed or overloaded

Increase the ramp-up-time.

Reduce the boost level (V/f control: P1311 & P1312, Vector control: P1610 & P1611)

A0502 Overvoltage

limit

Possible Causes

Overvoltage limit is reached

This warning can occur during ramp down, if the dc-link controller is disabled (P1240 = 0)

Diagnose & Remedy

Check the following:

Supply voltage (P0210) must lie within limits indicated on rating plate

DC-link voltage controller must be enabled (P1240) and parameterized properly

Ramp-down time (P1121) must match inertia of load

Required braking power must lie within specified limits

A0503 UnderVoltage

Limit

Possible Causes

Main supply failed

Main supply (P0210) and consequently DC-link voltage (r0026) below specified limit (P2172)

Diagnose & Remedy

Supply voltage (P0210) must lie within limits indicated on rating plate

Supply must not be susceptible to temporary failures or voltage reductions

Enable kinetic buffering (P1240 = 2)

A0504 Inverter

OverTemperature

Possible Causes

Warning level of inverter heat-sink temperature (P0614) is exceeded, resulting in pulse frequency
reduction and/or output frequency reduction (depending on parameterization in P0610)

Diagnose & Remedy

Check the following:

Load conditions and duty cycle must be appropriate

Fan must turn when inverter is running

Pulse frequency (P1800) must be set to default value

Ambient temperature could be higher than specified for the inverter

A0505 Inverter

I

2

t

Possible Causes

Warning level (P0294) exceeded, output frequency and/or pulse frequency will be reduced if
parameterized (P0290)

Diagnose & Remedy

Check the following: