Siemens MICROMASTER 411 User Manual

Page 73

Advertising
background image

Issue 03/01

5 System Parameters

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

73

ParNr ParText

Default

Acc

WS

QC

P1142[1]

BI: RFG enable setpoint

1:0

3

CT

N

P1230[1]

BI: Enable DC braking

0:0

3

CUT

N

P2103[1]

BI: 1. Faults acknowledgement

722:2

3

CT

N

P2104[1]

BI: 2. Faults acknowledgement

0:0

3

CT

N

P2106[1]

BI: External fault

1:0

3

CT

N

P2220[1]

BI: Fixed PID setp. select Bit 0

0:0

3

CT

N

P2221[1]

BI: Fixed PID setp. select Bit 1

0:0

3

CT

N

P2222[1]

BI: Fixed PID setp. select Bit 2

0:0

3

CT

N

P2235[1]

BI: Enable PID-MOP (UP-cmd)

19:13

3

CT

N

P2236[1]

BI: Enable PID-MOP (DOWN-cmd)

19:14

3

CT

N

Analogue I/O (P0004 = 8)

r0750

Number of ADCs

-

3

-

-

r0752[2]

Act. input of ADC [V]

-

2

-

-

P0753[1]

Smooth time ADC

3

3

CUT

N

r0754[2]

Act. ADC value after scaling [%]

-

2

-

-

r0755[2]

CO: Act. ADC after scal. [4000h]

-

2

-

-

P0756[1] Type

of

ADC

0

2 CT N

P0757[1]

Value x1 of ADC scaling [V]

0

2

CUT

N

P0758[1]

Value y1 of ADC scaling

0.0

2

CUT

N

P0759[1]

Value x2 of ADC scaling [V]

10

2

CUT

N

P0760[1]

Value y2 of ADC scaling

100.0

2

CUT

N

P0761[1]

Width of ADC deadband [V]

0

2

CUT

N

P0762[1]

Delay for loss of signal action

10

3

CUT

N

Setpoint Channel and Ramp Generator (P0004 = 10)

ParNr ParText

Default

Acc

WS

QC

P1000[1]

Selection of frequency setpoint

27

1

CT

Q

P1001[1] Fixed

frequency

1

0.00 2 CUT

N

P1002[1] Fixed

frequency

2

5.00 2 CUT

N

P1003[1] Fixed

frequency

3

10.00 2 CUT

N

P1004[1] Fixed

frequency

4

15.00 2 CUT

N

P1005[1] Fixed

frequency

5

20.00 2 CUT

N

P1006[1] Fixed

frequency

6

25.00 2 CUT

N

P1007[1] Fixed

frequency

7

30.00 2 CUT

N

P1016

Fixed frequency mode – Bit 0

1

3

CT

N

P1017

Fixed frequency mode – Bit 1

1

3

CT

N

P1018

Fixed frequency mode – Bit 2

1

3

CT

N

r1024

CO: Act. fixed frequency

-

3

-

-

P1031[1]

Setpoint memory of the MOP

0

2

CUT

N

P1032

Inhibit reverse direction of MOP

1

2

CT

N

P1040[1]

Setpoint of the MOP

5.00

2

CUT

N

r1050

CO: Act. Output freq. of the MOP

-

3

-

-

P1058[1]

JOG frequency right

5.00

2

CUT

N

P1059[1]

JOG frequency left

5.00

2

CUT

N

Advertising