A0922 no load applied to inverter, A0923 both jog left and jog right are requested, A0936 pid autotuning active – Siemens MICROMASTER 411 User Manual

Page 91: A0952 belt failure warning

Advertising
background image

Issue 03/01

6 Troubleshooting

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

91

DAC parameters should not be set to identical values, since this would produce illogical results.
Fault value = 0: Parameter settings for output identical

1: Parameter settings for input identical

2: Parameter settings for output do not correspond to DAC type

A0922 No load applied to inverter

Possible Causes

No Load is applied to the inverter.
As a result, some functions may not work as under normal load conditions.

A0923 Both JOG Left and JOG Right are requested

Possible Causes

Both JOG right and JOG left (P1055/P1056) have been requested. This freezes the RFG output
frequency at its current value.

A0936 PID Autotuning Active

Possible Causes

PID Autotuning (P2350) selected or running

A0952 Belt Failure Warning

Possible Causes

Load conditions on motor indicate belt failure or mechanical fault.

Diagnose & Remedy

Check the following:

No breakage, seizure or obstruction of drive train.

If using an external speed sensor, check for correct function. Check parameters:
P2192 (delay time for permitted deviation)

If using the torque envelope, check parameters:
P2182 (threshold frequency f1)
P2183 (threshold frequency f2)
P2184 (threshold frequency f3)
P2185 (upper torque threshold 1)
P2186 (lower torque threshold 1)
P2187 (upper torque threshold 2)
P2188 (lower torque threshold 2)
P2189 (upper torque threshold 3)
P2190 (lower torque threshold 3)
P2192 (delay time for permitted deviation)

Advertising