2.5.2

Line and Motor Connections

WARNING
This equipment must be grounded.

♦

Isolate the electrical power supply before making or changing connections to
the unit.

♦

MICROMASTERS must not be connected to a higher voltage supply.

♦

Ensure that the motor is configured for the correct supply voltage 380 V to
480 V three-phase supply.

♦

When synchronous motors are connected or when coupling several motors in
parallel, the inverter must be operated with voltage/frequency control
characteristic (P1300 = 0, 2 or 3).

CAUTION
After connecting the power and motor cables to the proper terminals, make sure
that the cover has been replaced properly before supplying power to the unit!

NOTICE

♦

Ensure that the appropriate circuit-breakers/fuses with the specified current
rating are connected between the power supply and inverter (see Section
7.5).

♦

Use Class 1 75

o

C copper wire only. For tightening torque see Section 7.3.

♦

To tighten up the power terminal screws use either a 4-5 mm flat bladed
screwdriver or a 2pt Pozidrive Head screwdriver.

Access to the power and motor terminals

The procedure for accessing the power and motor terminals on the
COMBIMASTER 411 & MICROMASTER 411 Inverter is illustrated in Figure 2-10.