3 quick commissioning (p0010=1) – Siemens MICROMASTER 411 User Manual

Page 53

Advertising
background image

Issue 03/01

3 Commissioning

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

53

Changing single digits in Parameter values

For changing the parameter value rapidly, the single digits of the display can be
changed by performing the following actions:
Ensure you are in the parameter value changing level (see "Changing parameters
with BOP").

1. Press (function button), which causes the right hand digit to blink.

2. Change the value of this digit by pressing

/

.

3. Press (function button) again causes the next digit to blink.
4. Perform steps 2 to 4 until the required value is displayed.

5. Press

the to leave the parameter value changing level.

NOTES
The function button may also be used to acknowledge a fault condition

3.3.4.2

Commissioning with the Advanced Operator Panel (AOP)

The Advanced Operator Panel (AOP) is available as an
option. Its advanced features include the following:

Multilingual clear text display

Upload/download facility for multiple parameter sets

Programmable via PC

Multidrop capability to drive up to 30 MICROMASTER
4’s

Please refer to the AOP Manual for details or contact your

local Siemens sales office for assistance.

3.3.4.3

Quick commissioning (P0010=1)

Mechanical and electrical installation of the inverter must be completed before
running „Quick Commissioning“.
It is important that the parameter P0010 is used for commissioning and P0003 for
selecting the parameter level (level). Quick commissioning particularly uses
parameters concerning the motor data and the acceleration and deceleration times.
Quick commissioning is ended with P3900. If this parameter is set to 1, it makes
the required motor calculations and sets all parameters which are not part of the
quick commissioning to the default values.

NOTE
Parameter P0399 = 0 must be set before starting quick commissioning because it
is not possible to change the motor data in the works default setting. Once quick
commissioning has been completed, P0399 = 2 must be set.

Advertising