Issue 03/01

4 Using the MICROMASTER 411 / COMBIMASTER 411

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

63

4.2

Command Sources (P0700)

NOTICE
The ramp times and ramp-smoothing functions also affect how the motor starts
and stops. For details of these functions, please refer to parameters P1120, P1121,
P1130 – P1134 in the Parameter List.

Starting the motor

Default

Terminal 1 (DIN 1): (P0700=2)

Other Settings

see P0700 to P0704

Stopping the motor

There are several ways to stop the motor:

Default:

OFF1 (4.3.1)

Terminal 1 (DIN 1): (P0700=2)

OFF2 (4.3.2)

Off button on BOP/AOP. Pressing the Off button once
(two seconds) or twice (with default settings). This is not
possible without BOP/AOP

OFF3 (4.3.3)

no standard setting

Other Settings

see P0700 to P0704

Reversing the motor

Default

Terminal 2 (DIN 2)

Other Settings

see P0700 to P0704


4.3

OFF and Braking Functions

4.3.1 OFF1

This command (produced by canceling the ON command) causes the inverter to
come to a standstill at the selected ramp-down rate.

Parameter to change ramp time see P1121

NOTICE

ON and the following OFF1 command must have the same source.

If the ON/OFF1 Command is set to more than one Digital input, only the last
set Digital Input is active e.g. DIN3 active.

OFF1 can be combined with DC braking or Compound braking.