Lennox Hearth ELITE EDVCRPM-B User Manual

Page 17

Advertising
background image

17

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

First Vent

Component
Align the dimple (four places)

with the opening of the locking

incline channel on appliance

collar. Twist vent component

clockwise to engage and seal.

Locking

Incline Channel

Dimple

Appliance collar

Vent / Appliance Collar

Connection

Align the dimple (four places) of the

upper vent section with the opening of

the locking incline channel on the

lower vent section. Twist vent

component clockwise to engage and

seal until arrow and dimple align.

Locking

Incline Channel

Dimple

Arrow

Connected

Vent Sections

Vent / Vent Section

Connection

Arrow

Arrow

Figure 26

Figure 27

Figure 29

Figure 28

C. Attach vent components to each other

- Other vent sections may be added to the

previously installed section in accordance with

the requirements of the vertical vent figures

and tables. To add another vent component

to a length of vent run, align the dimpled end

over the inclined channel end of the previously

installed section, adjusting the radial alignment

until the four locking dimples are aligned with

the inlets of the four incline channels of the

previous section.

Push the vent component against the previous

section until it fully engages, then twist the

component clockwise running the dimples down

and along the incline channels until they seat at

the end of the channels.This seating position

is indicated by the alignment of the arrow and

dimple as shown in Figure 28.

D. Install firestop/spacer at ceiling (Figure

29 ) - When using Secure Vent, use SV4.5VF

firestop/spacer at ceiling joists; when using

Secure Flex, use SF4.5VF firestop/spacer. If

there is living space above the ceiling level,

the firestop/spacer must be installed on the

bottom side of the ceiling. If attic space is

above the ceiling, the firestop/spacer must

be installed on the top side of the joist. Route

the vent sections through the framed opening

and secure the firestop/spacer with 8d nails

or other appropriate fasteners at each corner.

Remember to maintain 1" (25 mm) clearance

to combustibles, framing members, and attic

or ceiling insulation when running vertical

chimney sections. Attic insulation shield

(96K94) may be used to obtain the required

clearances indicated here. See installation

accessories tables on pages 38 and 39.

Vertical (Offset) Installation

Analyze the vent routing and determine the

quantities of vent sections and number of

elbows required. Refer to Vertical Vent Figures

and Tables on page 16 to select the type of

vertical installation desired. Vent sections are

available in net lengths of 4-1/2" (114 mm),

10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2"

(876 mm) and 46-1/2" (1181 mm). Refer to the

Effective Vent Length Chart Table 7 on page

16 for an aid in selecting length combinations.

Elbows are available in 90° and 45° configura-

tions. Refer to Figure 30 for the SV4.5E45 and

SV4.5E90 elbow dimensional specifications.

Where required, a telescopic vent section

(SV4.5LA) may be used to provide the installer

with an option in installing in tight and confined

spaces or where the vent run made up of fixed

length pieces develops a joint in a undesirable

location, or will not build up to the required

length. The SV4.5LA Telescopic Vent Section

has an effective length of from 1-1/2" (38 mm)

to 7-1/2" (191 mm). The SV4.5LA is fitted with

a locking inclined channel end (identical to a

normal vent section component) and a plain end

with 3 pilot holes. Slip the plain end over the

locking channel end of a standard SV4.5 vent

component the required distance and secure

with three screws.

Maintain a minimum 1" (25 mm) clearance to

combustible materials for all vertical elements.

Clearances for all horizontal elements are 3"

(76 mm) on top, 1" (25 mm) on sides and 1"

(25 mm) on the bottom.

A. Frame ceiling opening - Use a plumb line

from the ceiling above the appliance to locate

center of the vertical run. Cut and/or frame an

opening, 10-1/2" x 10-1/2" (267mm x 267mm)

inside dimensions, about this center mark

(Figure 26 ).

To attach a vent component to the appliance

collar, align the dimpled end over the collar,

adjusting the radial alignment until the four

locking dimples are aligned with the inlet of

the four inclined channels on the collar (refer to

Figure 27 ). Push the vent component against

the collar until it fully engages, then twist the

component clockwise, running the dimples

down and along the incline channels until they

seat at the end of the channels. The unitized

design of the Secure Vent components will

engage and seal both the inner and outer pipe

without the need for sealant or screws. If desired

a #6 x 1/2" screw may be used at the joint, but

it is not required as the pipe will securely lock

when twisted.

Note: An elbow may also be attached to the

appliance collar. Attach in the same manner

as you would a vent section.

B. Attach vent components to appliance -

Secure Vent SV4.5 direct vent system compo-

nents are unitized concentric pipe components

featuring positive twist lock connections (see

Figures 27 and 28 ).

All of the appliances covered in this document

are fitted with collars having locking inclined

channels. The dimpled end of the vent com-

ponents fit over the appliance collar to create

the positive twist lock connection.

1” (25.4 mm)

Minimum

Clearance to

Combustibles

8 ft. (2.4 M)

Maximum

v

SV4.5VF

Firestop / spacer

u

SV4.5SP

Support Plate

u

SV4.5SU

Support Strap

Shown With

Optional

Radiant

Panels

u

Secured

to Vent with

Appropriate

Fasteners

Ceiling

Framing

v

When

using

secure

Flex, use

Firestop/

Spacer

SF4.5VF

SV4.5FA or

SV4.5FB Flashing

and SV4.5SC

Storm Collar

SV4.5CGV-1

Termination

10-1/2" Min.

(267 mm)

10-1/2" Min.

(267 mm)

Advertising