Warning – Lennox Hearth ELITE EDVCRPM-B User Manual

Page 19

Advertising
background image

19

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

VERTICAL VENT FIGURES/TABLES

Note: Secure Vent (rigid vent pipe) is shown

in the figures; Secure Flex (flexible vent pipe)

may also be used.

Note: It is very important that the horizontal/

inclined run be maintained in a straight (no

dips) and recommended to be in a slightly

elevated plane, in a direction away from the

fireplace of 1/4" rise per foot (20 mm per meter)

which is ideal, though rise per foot run ratios

that are smaller are acceptable all the way down

to at or near level.

Note: SV4.5VF (Secure Vent), SF4.5VF (Secure

Flex) firestop/spacer must be used anytime vent

pipe passes through a combustible floor or ceil-

ing. SV4.5HF (Secure Vent), SF4.5HF (Secure

Flex)firestop/spacer must be used anytime vent

pipe passes through a combustible wall.

Note: Two 45 degree elbows may be used in

place of one 90 degree elbow. The same rise

to run ratios, as shown in the venting figures

for 90 elbows, must be followed if 45 degree

elbows are used.

Note: An elbow is acceptable as 1 foot of

vertical rise, except where an elbow is the

only vertical component in the system. (See

Figure 44 on page 23 ).

WARNING

Under no circumstances, may sepa-

rate sections of concentric flexible

vent pipe be joined together.

H

V

V1

V

H

Figure 35

- Top Vent - STRAIGHT

Figure 37

- Top Vent - TWO 90 DEGREE ELBOWS

40 feet

(12.2 meters)

Maximum

u

Ceiling Firestop /

Spacer (SV4.5VF)

u

When using Secure Flex, use

Firestop/Spacer SF4.5VF

u

Ceiling Firestop /

Spacer (SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

Ceiling Firestop / Spacer (SV4.5VF)

u

When using Secure Flex, use

Firestop / Spacer SF4.5VF.

v

When using Secure Flex, use

Firestop / Spacer SF4.5HF.

Example: If 20 feet of (H) hori-

zontal vent run is needed, then 4

feet minimum of (V) vertical vent

will be required.

This table shows a 1(V) to 5(H)

ratio. For every 1 foot of (V) verti-

cal, you are allowed 5 feet of (H)

horizontal run, up to a maximum

horizontal run of 20 feet.

An elbow is acceptable as 1 foot

of vertical rise except where

an elbow is the only vertical

component in the system. See

Figure 44.

Table B

H Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + V

1

+ H = 40 feet (12.2 m) Max.

H = 20 feet (6.096 meters) Max.

Table A

H Maximum

V Minimum

feet

(meter)

feet

(meter)

2

(0.610)

1

(0.305)

4

(1.219)

2

(0.610)

6

(1.829)

3

(0.914)

8

(2.438)

4

(1.219)

V + H = 40 feet (12.2 meters) Max.

H = 8 feet (2.4 meters) Max.

Ratio V to H ratio is 1:2

u

When using Secure Flex, use Firestop /

Spacer SF4.5VF.

Example: If 8 feet of (H) horizontal vent run is needed, then 4 feet minimum (V) vertical vent will be

required.
This table shows a 1(V) to 2(H) ratio. For every 1 foot of (V) vertical, you are allowed 2 feet of (H)

horizontal run, up to a maximum horizontal run of 8 feet.

Figure 36

- Side Vent - ONE 90 DEGREE ELBOW

A Vent Restrictor as

shown in Figure 24,

must be used in this

application.

Advertising