Lennox Hearth ELITE EDVCRPM-B User Manual

Page 24

Advertising
background image

24

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

HORIZONTAL VENT FIGURES/TABLES (continued)

H1

V

H

V

H

H1

u

When using Secure Flex, use Firestop

/ Spacer SF4.5VF

v

When using Secure Flex, use Firestop

/ Spacer SF4.5HF

u

When using Secure Flex, use Firestop /

Spacer SF4.5VF

v

When using Secure Flex, use Firestop /

Spacer SF4.5HF

u

Ceiling Firestop

/ Spacer (SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

Ceiling Firestop

/ Spacer (SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

v

Wall Firestop/

Spacer (SV4.5HF)

Table G

H

+H

1

Maximum

H

Maximum

V Minimum

feet

(meter)

feet

(meter)

feet

(meter)

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + H + H1 = 40 feet (12.2 m) Max

H = 8 feet (2.438 meters) Max.

H + H1 = 20 feet (6.096 meters) Max.

Example: If 20 feet of (H + H

1

) horizontal vent

run is needed, then 4 feet minimum of (V) vertical

vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1

foot of (V) vertical, you are allowed 5 feet of (H+

H

1

) horizontal run, up to a maximum horizontal

run of 20 feet.

Table H

H

+ H

1

Maximum

V Minimum

feet

(meter)

feet

(meter)

3

(0.914)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V +

H

+ H

1

= 40 feet (12.2 m) Max.

H

+ H

1

= 20 ft. (6.096 m) Max.

Figure 45

- Side Vent, TWO 90 DEGREE ELBOWS

Figure 46

- Top Vent, TWO 90 DEGREE ELBOWS

Square termination

(SV4.5HT-2) shown

Square termination

(SV4.5HT-2) shown

See Table 8 on Page 23 as an aid in venting

component selection for a particular range of

exterior wall thicknesses.

See Table 8 on Page 23 as an aid in venting

component selection for a particular range

of exterior wall thicknesses.

Example: If 20 feet of (H + H

1

) horizontal vent run

is needed, then 4 feet minimum of (V) vertical vent

will be required.

This table shows a 1(V) to 5(H) ratio. For every 1

foot of (V) vertical, you are allowed 5 feet of (H+

H

1

) horizontal run, up to a maximum horizontal

run of 20 feet.

An elbow is acceptable as 1 foot of vertical rise except

where an elbow is the only vertical component in

the system. See Figure 44.