Lennox Hearth ELITE EDVCRPM-B User Manual

Page 21

Advertising
background image

21

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

The unitized design of the Secure Vent compo-

nents will engage and seal both the inner and

outer pipe elements with the same procedure.

Sealant and securing screws are not required.

Note: An elbow may also be attached to the

appliance collar. Attach in the same manner

as you would a vent section.

Remember to maintain 1" (25 mm) clearance

to combustibles, framing members, and attic

or ceiling insulation when running vertical

chimney sections.

HORIZONTAL (OUTSIDE WALL)

TERMINATION SYSTEM

F. Install firestop/spacer at ceiling -

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex,

use SF4.5VF firestop/spacer. If there is living

space above the ceiling level, the firestop/

spacer must be installed on the bottom side of

the ceiling. If attic space is above the ceiling,

the firestop/ spacer must be installed on the

top side of the joist. Route the vent sections

through the framed opening and secure the

firestop/spacer with 8d nails or other appropriate

fasteners at each corner.

Secure Vent SV4.5 direct vent system components

are unitized concentric pipe components featuring

positive twist lock connection, (refer to Figure 28

on page 17). All of the appliances covered in this

document are fitted with collars having locking

inclined channels. The dimpled end of the vent

components fit over the appliance collar to create

the positive twist lock connection.

A. Plan the vent run -

Analyze the vent routing and determine the

types and quantities of sections required

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572

mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net

section lengths are available. It is recommended

that you plan the venting so that a joint does not

occur in the ceiling or roof joists. Allow for elbows

as indicated in Figure 30 on page 18.

Maintain a minimum 1" (25 mm) clearance to

combustibles on the vertical sections. Clearances

for the horizontal runs are; 3" (76 mm) on top, 1" (25

mm) on sides, and 1" (25 mm) at the bottom.

B. Frame exterior wall opening -

Locate the center of the vent outlet on the exterior

wall according to the dimensions shown in Figures

13, through 16 on page 11. Cut and/or frame an

opening, 10-1/2" x 12-1/8" (267 mm x 308mm)

inside dimensions, about this center.

C. Frame ceiling opening - If the vertical route

is to penetrate a ceiling, use plumb line to locate

the center above the appliance. Cut and/or frame

an opening, 10-1/2" x 10-1/2" (267 mm x 267

mm) inside dimensions, about this center (refer

to Figure 26 on page 17 ).

G. Support the vertical run sections -

On the vertical run, support the venting sys-

tem every 8 feet (2.4m) above the fireplace

vent outlet with field provided support straps

(Plumber's tape). Attach the straps to the vent

pipe and secure to the framing members with

nails or screws. See Figure 29 on page 17.

H. Change vent direction - At transition

from or to a horizontal/inclined run, install the

SV4.5E45 and SV4.5E90 elbows in the same

manner as the straight vent sections. The

elbows feature a twist section to allow them

to be routed about the center axis of their

initial collar section to align with the required

direction of the next vent run element. Twist

elbow sections in a clockwise direction only

so as to avoid the possiblity of unlocking any

of the previously connected vent sections.

See Figure 30 on page 18.

I. Continue installation of horizontal/inclined

sections - Continue with the installation of the

straight vent sections in horizontal/inclined run

as described in Step E. Install support straps

every 5 ft. (1.52 m) along horizontal/inclined

vent runs using conventional plumber’s tape.

See Figure 40, it is very important that the

horizontal/inclined run be maintained in a

straight (no dips) and recommended to be in

a slightly elevated plane, in a direction away

from the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal, though rise per foot

run ratios that are smaller are acceptable all the

way down to at or near level. Use a carpenter’s

level to measure from a constant surface and

adjust the support straps as necessary.

E. Attach vent components to each other - Other

vent sections may be added to the previously

installed section in accordance with the require-

ments of the vent tables. To add another vent

component to a length of vent run, align the

dimpled end of the component over the inclined

channel end of the previously installed section,

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four

incline channels of the previous section. Push

the vent component against the previous section

until it fully engages, then twist the component

clockwise running the dimples down and along

the incline channels until they seat at the end of

the channels.This seating position is indicated

by the alignment of the arrow and dimple as

shown in Figure 28 on page 17.

D. Attach vent components to appliance - To

attach a vent component to the appliance collar,

align the dimpled end over the collar, adjusting the

radial alignment until the four locking dimples are

aligned with the inlets of the four incline channels

on the collar (refer to Figure 27 on page 17 ).

Both of these horizontal vent systems terminate

through an outside wall. Building Codes limit or

prohibit terminating in specific areas. Refer to

Figure 6 and page 7 for location guidelines.

Figures 40, and Figures 43 to 48 on pages

23 to 25 and their associated Horizontal Vent

Table illustrate the various horizontal venting

configurations that are possible for use with

these appliances. Secure Vent pipe applications

are shown in these figures; Secure Flex pipe

may also be used. A Horizontal Vent Table sum-

marizes each system’s minimum and maximum

vertical and horizontal length values that can be

used to design and install the vent components

in a variety of applications.

Push the vent component against the collar until it

fully engages, then twist the component clockwise,

running the dimples down and along the incline chan-

nels until they seat at the end of the channels.

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides

for all vertical runs; and 3" (76 mm) at the top,

1" (25 mm) at sides, and 1" (25 mm) at the

bottom for all horizontal/inclined runs

Figure 40 -

TYPICAL HORIZONTAL VENT INSTALLATION

Horizontal / Inclined Run

Support

Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

u

Firestop / Spacer

SV4.5VF

u

When Using Secure Flex,

Use Firestop / Spacer SF4.5VF

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

SV4.5HT-2

Termination

Shown

Support Bracket Spacing

Every 5 ft (1.52 m)

Exterior

Wall

SV4.5HT-2

Termination

Shown

Shown With Optional Radiant Panels

See Figure 29 on Page 17 for

vertical vent section support.

Advertising