Lennox Hearth ELITE EDVCRPM-B User Manual

Page 25

Advertising
background image

25

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

HORIZONTAL VENT FIGURES/TABLES (continued)

V

H2

H1

H

Table J

H

+ H

1

+ H

2

Maximum

H

Maximum

V Minimum

feet

(meter)

feet (meter) feet

(meter)

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + H + H1 + H2 = 40 feet (12.2 m) Max

H = 8 feet (2.438 meters) Max.

H + H1+ H2 = 20 feet (6.096 meters) Max.

Example: If 20 feet total (H+H

1

+H

2

)

horizontal vent run is needed, then 4

feet minimum of (V) vertical vent will

be required.
This table shows a 1(V) to 5(H) ratio.

For every 1 foot of (V) vertical, you

are allowed 5 feet of horizontal run

up to a maximum total (H+H

1

+H

2

)

horizontal run of 20 feet.

Table K

H

+ H

1

Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

H

+ H

1

= 20 feet (6.096 m) Max.

V

+ V

1

+

H

+ H

1

= 40 ft. (12.192 m) Max.

V

H

H1

V1

v

Wall Firestop / Spacer

(SV4.5HF)

u

Ceiling Firestop /

Spacer (SV4.5VF)

u

Ceiling Firestop /

Spacer (SV4.5VF)

v

Wall Firestop

/ Spacer (SV4.5HF)

v

Wall Firestop / Spacer

(SV4.5HF)

Figure 47

- Side Vent, THREE 90 DEGREE ELBOWS

Square termination (SV4.5HT-2) shown

Square termination

(SV4.5HT-2) shown.

Figure 48

- Top Vent, THREE 90 DEGREE ELBOWS

u

When using Secure Flex, use

Firestop / Spacer SF4.5VF

v

When using Secure Flex, use

Firestop / Spacer SF4.5HF

Note: See Table 8 as an aid in

venting component selection for

a particular range of exterior wall

thicknesses.

u

When using Secure Flex,

use Firestop / Spacer

SF4.5VF

v

When using Secure Flex,

use Firestop / Spacer

SF4.5HF

Note:

See Table 8 as an aid

in venting component selec-

tion for a particular range of

exterior wall thicknesses.

Example: If 20 feet total (H+H

1

) horizontal

vent run is needed, then 4 feet minimum of

(V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For

every 1 foot of (V) vertical, you are allowed

5 feet of (H+ H

1

) horizontal run, up to a

maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of verti-

cal rise except where an elbow is the only

vertical component in the system. See

Figure 44.