Edge 60 pellet fireplace – Quadra-Fire EDGE 60 ZERO CLEARANCE PELLET FIREPLACE 7051-158B User Manual

Page 45

Advertising
background image

R

December 6, 2011

7051-158B

Page 45

EDGE 60 Pellet Fireplace

Non-combustible
Hearth Extension

Clean-out
Cover

Tee

Wall Thimble

Support
Bracket
every 60 in.
(1524mm)

12 in.
(305mm)
minimum

Termination
Cap

Flashing

0 in. (0mm) to Standoff

6 in. (152mm)

minimum

Firestop

Flashing

Termination
Cap

6 in.

(152mm)

Min.

Non-combustible
Hearth Extension

1 in. (25mm)
Minimum
*See Note

12 in.
(305mm)
Minimum

0 in. (0mm) to
Standoff

J. Vertical - Interior - Typical Installation

K. Through the Wall & Vertical - Exterior

Figure 44.1

Figure 44.2

We recommend a minimum of 60 inches (1.52m) verti-
cal, however above the eave is preferred.

Both installations are approved for mobile home instal-
lations. Must use 3 or 4 inch (76mm to 102mm) “L”
or “PL” Listed pellet venting or Listed double wall pipe
and Quadra-Fire Outside Air Kit in all installations.
Single wall pipe is approved for residential installa-
tions only.

*NOTE: Clearance to combustibles are for 1 inch
(25mm) clearance approved pellet pipe. If pellet pipe
has a 2 inch or 3 inch (51mm or 76mm) air clearance
to combustibles, increase the clearance from rear
standoff accordingly to meet pipe manufacturer clear-
ance requirements