Mobile home installation, Caution – Quadra-Fire EDGE 60 ZERO CLEARANCE PELLET FIREPLACE 7051-158B User Manual

Page 47

Advertising
background image

R

December 6, 2011

7051-158B

Page 47

EDGE 60 Pellet Fireplace

3.

The appliance must be secured to the mobile home
structure by bolting it to the fl oor. See page 33 for
detailed instructions on securing fireplace to the
fl oor.

4.

The appliance must be grounded with #8 solid copper
grounding wire or equivalent, terminated at each end
with an NEC approved grounding device.

5.

Refer to Clearances to Combustibles and fl oor protec-
tion requirements in Section 6 for listings to combus-
tibles and appropriate chimney systems.

6. Use silicone to create an effective vapor barrier at

the location where the chimney or other component
penetrates to the the exterior of the structure.

7.

Follow the chimney manufacturer’s instructions when
installing the vent system for use in a mobile home.

8. Installation shall be in accordance with the Manufacturers

Home & Safety Standard (HUD) CFR 3280, Part 24.

SparkArrestor Cap

Roof Flashing

Storm Collar

Joist Shield/Firestop

Approved Class L
or PL Pellet Vent

Figure 46.1

9

Mobile Home Installation

WARNING! Risk of Asphyxiation!

Never install in a sleeping room.

Consumes oxygen in the the room.

R

emain clear of leaves, debris, ice and/or snow.

• Be unrestricted while the appliance is in use to pre-

vent room air starvation which causes smoke spill-
age.

Smoke spillage can also set off smoke alarms.

1.

An outside air intake must be provided for the combus-
tion air and must:

2.

The combustion air duct system must be made of metal
and it must:

P

ermit zero clearance to combustible construction.

• Prevent material from dropping into the inlet or into

the area beneath the dwelling.

• Must

contain a rodent screen.

CAUTION

THE STRUCTURAL INTEGRITY OF THE MOBILE HOME
FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-
TAINED

Do NOT cut through:
• Floor joist, wall, studs or ceiling trusses.
• Any supporting material that would affect the structural

integrity.

This unit is to be connected to a factory-built chimney
conforming to CAN/ULC-S629, Standard for 650°C
Factory-Built Chimneys.

For removal of the chimney for mobile home transporta-
tion, contact the proper transportation offi cials.