Troubleshooting for installers, Edge 60 pellet fireplace – Quadra-Fire EDGE 60 ZERO CLEARANCE PELLET FIREPLACE 7051-158B User Manual

Page 52

Advertising
background image

Page 52

7051-158B

December 6, 2011

R

EDGE 60 Pellet Fireplace

With proper installation, operation, and maintenance your appli-
ance will provide years of trouble-free service. This trouble-
shooting guide shall be used by a qualifi ed service technician
only).

Error Message

Possible Cause

Corrective Action

Bad wall control or control board
3 wires have loose connections or installed
wrong

Replace wall control or control board
Check connections

BAD TC DROP TUBE

(TC = Thermocouple)

Drop tube thermocouple is broken or leads are
reversed

Check connections

Replace thermocouple

BAD TC FIREPOT

(TC = Thermocouple)

Firepot thermocouple is broken or leads are
reversed

Check connections

Replace thermocouple

SNAP DISC TRIPPED

Overheat sensor (snap disc) has tripped

Convection blower may need cleaning

Turn power off to appliance and manually
reset snap disc then turn power back on

Clean convection blower if needed

VACUUM SW ERROR

(SW = Switch)

Vacuum switch is bad

Vacuum hose is plugged/disconnected

Check connections. Bypass vacuum with
jumper wire, if runs, switch is bad. Replace
switch

Check vacuum hose

COMB BLOWER JAMMED

Combustion blower is blocked/jammed

Remove blockage

Replace blower if necessary

Turn the power switch OFF and then back
ON to clear the error

AUGER JAMMED

Auger jammed, feed motor bad

Pull the feed system and inspect

Clear jam and Press Retry

MISSED IGNITION

Igniter bad or poor harness connection

Out of fuel or fuel is bridging in hopper

Faulty fi repot thermocouple connection has
shorted.

Check connections, if OK replace igniter

Break up bridging pellets. Refi ll hopper

Replace the thermocouple
Press Retry

MIN FIREPOT TEMP

Out of fuel

Refi ll hopper

Add handful of pellets to fi repot to prime it

Press Retry

MAX DROP TUBE TEMP

Stove in over-heat condition

Flame height set too high

Components may need cleaning

Confi rm setting matches burning fuel

Adjust fl ame height

Clean the fi rebox, heat exchanger, convec-
tion blower, fi repot and ash pan

CONV BLOWER JAMMED

Convection blower blocked/jammed

Remove blockage

Replace blower if necessary

Turn the power switch OFF and then back
ON to clear the error

CHECK ASHPAN

Auto-clean jammed

Auto-clean switch is bad

Linkage has become disconnected

If ashpan is empty, check for a jam. Use a
screw driver and fi rmly push in the fi repot
fl oor holes and fl ex spring and push toward
home to release jam

Replace switch

Reconnect linkage

SCREEN GOES BLANK

Static discharge or nearby lightning or

Electric fast transients at the input mains

Power switch in OFF position

Wait 25 seconds and press any key to
refresh the screen.

Turn to ON position

Hopper lid not closed all the way

Switch is out of adjustment (auger will not
function)

Close the lid. If that didn’t work replace the
switch

Adjust or replace switch

Firebox door is not latched properly

Fireplace not rolled in completely

Slide rail bolts not installed

Adjust or replace door switch

Replace interlock switch or magnet

Install bolts

Out of fuel

Check fuel level, if OK the switch may be
out, replace switch

12

Troubleshooting For Installers