7-2. Operation Data

<Cooling>

Tempeature

Model name

Standard

Heat exchanger

Indoor

Outdoor

Compressor

condition [°F (°C)] RAS- pressure pipe temp. fan mode fan mode revolution

Indoor Outdoor P [psi (MPa)] T1 [°F (°C)] T2 [°F (°C)] (rps)

80/67

98/75

131 to 160

52 to 55

40 to 42

(26.7/19.4)

(35/23.9)

(0.9 to 1.1)

(11 to 13)

(37 to 39)

131 to 160

52 to 55

40 to 42

(0.9 to 1.1)

(11 to 13)

(42 to 44)

<Heating>

Tempeature

Model name

Standard

Heat exchanger

Indoor

Outdoor

Compressor

RAS- pressure pipe temp. fan mode fan mode revolution

Indoor

Outdoor

(rps)

70/60

47/43

363 to 392

102 to 105

32 to 37

(21.1/15.6)

(8.3/6.1)

(2.5 to 2.7)

(39 to 41)

(0 to 3)

377 to 406

106 to 106

32 to 36

(2.6 to 2.8)

(41 to 43)

(0 to 2)

NOTES :

1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.

(Thermistor themometer)

2. Connecting piping condition : 25 ft (7.5m)

74

High

High

82

15LKV-UL

17LKV-UL

High

High

17LKV-UL

High

High

62

High

High

57

15LKV-UL

131 to 160

52 to 55

41 to 43

(0.9 to 1.1)

(11 to 13)

(42 to 44)

22LKV-UL

High

High

88

116 to 145

52 to 55

104 to 107

(0.8 to 1.0)

(11 to 13)

(42 to 44)

22LKV-UL

High

High

84

FILE NO. SVM-10020

– 23 –

condition [°F (°C)]

P [psi (MPa)] T1 [°F (°C)] T2 [°F (°C)]