Toshiba CARRIER RAS-15LKV-UL User Manual

Page 32

Advertising
background image

– 32 –

Item

3. Outdoor fan

motor control

Operation flow and applicable data, etc.

The blowing air volume at the outdoor unit side is controlled.

Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.

* For the fan motor, a DC motor with non-stage variable

speed system is used. However, it is limited to 8 stages for
reasons of controlling.

Description

1) The operation command sent

from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.

2) When strong wind blows at

outdoor side, the operation of air
conditioner continues with the
fan motor stopped.

3) Whether the fan is locked or not

is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.

4) According to each operation

mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.

Outdoor fan speed (rpm)

Tap

f 1

f 2

f 3

f 4

f 5

f 6

f 7

230

300

350

410

480

500

530

Tap

f 9

f A

f B

f C

f D

f E

f F

640

640

670

670

700

700

800

800

800

800

900

1000

900

1000

RAS-15LAV-UL

RAS-17LAV-UL

f 0

0

RAS-15LAV-UL

RAS-17LAV-UL

RAS-22LAV-UL

230

300

350

410

480

500

530

0

230

300

350

410

480

500

530

0

f 8

560

560

RAS-22LAV-UL

640

670

750

920

920

1000

1000

560

Tap

f 1

f 2

f 3

f 4

f 5

f 6

f 7

230

300

350

410

480

500

530

Tap

f 9

f A

f B

f C

f D

f E

f F

640

640

670

670

700

700

800

800

800

800

900

1000

900

1000

RAS-15LAV-UL

RAS-17LAV-UL

f 0

0

RAS-15LAV-UL

RAS-17LAV-UL

RAS-22LAV-UL

230

300

350

410

480

500

530

0

230

300

350

410

480

500

530

0

f 8

560

560

RAS-22LAV-UL

640

670

750

920

920

1000

1000

560

To

≥ 100°F (38°C)

To

≥ 82°F (28°C)

To

≥ 59°F (15°C)

To

≥ 42°F (5.5°C)

To

≥ 32°F (0°C)

To

≥ 22°F (-5°C)

To

≥ 50°F (10°C)

To

≥ 42°F (5.5°C)

To

≥ 22°F (-5°C)

To <

22°F (-5°C)

To

≥ 50°F (10°C)

To

≥ 42°F (5.5°C)

To

≥ 22°F (-5°C)

To

<

22°F (-5°C)

FILE NO. SVM-10020

In cooling operation

Compressor speed (rps)

To

During ECO,

QUIET and

comfort sleep

When To is abnormal

< 22.1

< 50.3

50.3 <

MIN MAX MIN MAX MIN MAX

f 6

f 9

f 8

f B

f A

f E

f 5

f 9

f 7

f B

f 9

f E

f 3

f 7

f 5

f 9

f 7

f B

f 1

f 3

f 1

f 7

f 3

f 9

f 1

f 3

f 1

f 5

f 3

f 7

f 0

f 1

f 0

f 3

f 1

f 4

f 6

f 9

f 8

f B

f A

f B

f 5

f 9

f 7

f B

f 9

f B

f 3

f 7

f 5

f 9

f 7

f B

f 1

f 3

f 1

f 7

f 3

f 9

f 1

f 3

f 1

f 5

f 3

f 7

f 0

f 1

f 0

f 3

f 1

f 4

f 1

f F

f 1

f F

f 1

f F

In Heating operation

Compressor speed (rps)

To

During

ECO mode

When To is abnormal

< 30.5

< 55.1

55.1 <

f 6

f 8

f 9

f 8

f A

f C

f A

f B

f D

f A

f B

f D

f 5

f 7

f 9

f 7

f 9

f B

f 9

f A

f B

f 9

f A

f B

f D

f D

f D

To

≥ 100°F (38°C)

To

≥ 82°F (28°C)

To

≥ 59°F (15°C)

To

≥ 42°F (5.5°C)

To

≥ 32°F (0°C)

To

≥ 22°F (-5°C)

Air conditioner ON

(Remote controller)

YES

YES

NO

NO

Indoor unit controller

Fan motor ON

3) Fan lock

4) Motor operates as shown in the table below.

1) Outdoor unit
operation

command

(Outdoor

fan

control)

Air conditioner

OFF

Alarm

display

2) Fan speed

≥ 400.

(by strong wind)

when the motor OFF.

Fan motor OFF continues

(Use wind for heat

exchanging)