Operation of diagnosis function

Check

code

Block

Check

code

Cause of operation

Air

conditioner

status

Display flashing

error

Outdoor P.C.

Current on inverter circuit

All OFF

Flashes after

1. Remove connecting lead wire of the

board

is over limit in short time.

error is detected

compressor, and operate again.

Inverter P.C. board is

4 times*.

2. If outdoor fan does not operate or

failure, IGBT shortage, etc.

operat

e but stop after some period,

Compressor current is

replace the inverter P.C. board.

higher than limitation,

3. If outdoor fan operates normally,

lock rotor, etc.

measure 3-Phase output of inverter

P.C. board (150-270VAC) at the

connecting lead wire of compressor.

4. If 3-Phase output is abnormal, replace

inverter P.C.Board.

5. If 3-Phase output is normal, replace

compressor. (lock rotor, etc.)

Compressor position-detect

All OFF

Flashes after

1. Remove connecting lead wire of the

circuit error or short-circuit

error is detected

compressor, and operate again.

between winding of

4 times*.

2. If outdoor fan does not operate or

compressor.

operation but stop after some period,

replace the inverter P.C. board.

3. If outdoor fan operates normally,

measure resistance of compressor

winding. If circuit is shortage, replace

the compressor.

Current-detect circuit of

All OFF

Flashes after

Even if trying to operate again, all

inverter P.C. board error.

error is detected

operations stop, replace inverter

4 times*.

P.C. board.

TE sensor ; The heat

All OFF

Flashes after

1. Check sensors TE, TS and connection.

exchanger temperature

error is detected

2. In case of the sensors and its

sensor of the outdoor unit

4 times*.

connection is normal, check the

either TS sensor ; Suction

inverter P.C. board.

pipe temperature sensor,

out of place, disconnection

or shortage.

TD sensor ; Discharge pipe

All OFF

Flashes after

1. Check sensors TD and connection.

temperature sensor is

error is detected

2. In case of the sensor and its

disconnection or shortage.

4 times*.

connection is normal, check the

inverter P.C. board.

Outdoor fan failure or its

All OFF

Flashes after

1. Check the motor, measure winding

drive-circuit on the inverter

error is detected

resistance, shortage or lock rotor.

P.C. board failure.

4 times*.

2. Check the inverter P.C. board.

TO sensor ; The outdoor

Operation

Record error

1. Check sensors TO and connection.

temperature sensor is

continues.

after detected

2. In case of the sensor and its

disconnection or shortage.

4 times*.

connection is normal, check the

But does not

inverter P.C. board.

flash display.

Action and Judgment