Initial setting of "Cooling storage position"
Louver : Horizontal blowing (37.4°)

Heating operation/

AUTO (HEAT)

Initial setting of “Heating storage position”
Louver : Directs downward (76.9˚)

Item

8. Louver control

1) Louver

position

Operation flow and applicable data, etc.

This function controls the air direction of the indoor unit.

Description

3) Swing

2) Louver position in heating operation

2) Air direction adjustment

• The position is automatically controlled according to the operation

• The set louver position is stored in memory by the microcomputer,

The angle of the louver is indicated as the louver closes fully is 0°.

1) Louver position in cooling operation

mode (COOL/HEAT).

and the louver returns to the stored position when the next operation

is performed. (Cooling/Heating memory position)

• Swing

When pressing
[SWING] button during
operation, the louver
starts swinging.

• The louver position can

be arbitrarily set up by
pressing [FIX] button.

– 36 –

FILE NO. SVM-10020

Cooling operation/

AUTO (COOL)

• Swing operation is perfor in range 35° with the Fixed position as

the center.

• If the swing range exceeded either upper or lower limit position,

swing operation is performed in range 35° from the limit.

Fixed
Position
before start
swing

Upper Limit
Position.

Lower Limit
Position

30

o

5

o

Swing
range 35

o

Upper Limit
Position.

Lower Limit
Position.

Fixed Position
before start
swing.

17.5

o

17.5

o

Swing
range 35

o