Operation of diagnosis function

Check

code

Block

Check

code

Cause of operation

Air

conditioner

status

Display flashing

error

Compressor drive output error.

All OFF

Flashes after

1. Check installation conditions such as

(Relation of voltage, current

error is detected

packed valve opening, refrigerant

and frequency is abnormal)

4 times*.

amount and power supply (rate +10%,

Overloading operation of

both of operation and non operation

compressor caused by

condition).

over-charge refrigerant,

2. Check P.M.V. by measure the

P.M.V. failure, etc.

resistance of the coil and confirm its

Compressor failure (High

operation (sound of initial

current).

operation, etc.)

3. Observe any possibility cause which

may affect operation load of

compressor.

4. Operate again. If compressor

operation is failure when 20 seconds

passed (count time from operation

starting of compressor), replace

compressor.

* 4 times ; When first error is detected, error is count as 1 time, then once operation is stop and re-started.

After re-starting operation within 6 minutes, if same error is detected, error count is add (count become 2 times)

When error count comes 4 times, record error to check code. But after re-starting operation, if no error is

detected and air conditioner can operate more than 6 minutes, error count is cleared.

The others

Return signal of the outdoor

Indoor unit

Flashes when

1. Check power supply (Rate + 10%)

(including

unit has been sent when

operates

error is detected. 2. If the air conditioner repeat operates

compressor)

operation start. But after

continue.

Flashing stop

and stop with interval of approx. 10

that, signal is stop some time.

Outdoor unit

and outdoor unit

to 40 minutes.

Instantaneous power

stop.

start to operate

Check protector (hardware) such

failure.

when the return

as Hi-Pressure switch,

Some protector

signal from the

Thermal-Relay, etc.

(hardware) of the

outdoor unit is

Check refrigerant amount, packed

outdoor unit open

normal.

valve opening and any possibility

circuit of signal.

cause which may affect high

Signal circuit of indoor

temperature or high pressure.

P.C. board or outdoor

3. Check operation signal of the indoor

P.C. board is failure

unit by using diode. Measure voltage

in some period.

at terminal block of the indoor unit

between No.2 and No.3 (or L2 and S)

If signal is varied 15-60V continuously,

replace inverter P.C. board.

If signal is not varied, replace indoor

P.C. board.

Action and Judgment

FILE NO. SVM-10020