– 39 –

Item

12. Pulse

Modulating
valve (P.M.V.)

Operation flow and applicable data, etc.

This function controls throttle amount of the

refrigerant in the refrigerating cycle.
According to operating status of the air conditioner,

this function also controls the open degree of valve

with an expansion valve with pulse Modulation.

Description

1) When starting the operation, move the

valve once until it fits to the stopper.

(Initialize)
* In this time, “Click” sound may be

heard.

2) Adjust the open degree of valve by super

heat amount. (SH control)

3) If the discharge temperature was exces-

sively up, adjust the open degree of valve

so that it is in the range of set tempera-

ture. (Discharge temp. control)

* SH (Super Heat amount) =

Ts (Temperature of suction pipe of the compressor) –

Tc or Te (Heat exchanger temperature at evaporation side)

* PMV: Pulse Modulating Valve

Starting up

Initialize

Move to

initial position

PMV open degree control

SH control

Td

release control

Turn OFF by

remote controller

Move to "Stop

Compressor Stop by

"Room Temperature

Compressor ON

Defrosting

operation

Control"

Position" (Setup

from factory)

Move to "Defrost

Position" (Setup

from factory)

control

FILE NO. SVM-10020

4) When defrost operation is performed, the

open degree of valve is adjusted accord-

ing to each setup conditions during

preparation for defrost and during defrost

operation (4-way valve is inversed.).

5) When operation is OFF by the remote

controller or when compressor is OFF by

room temperature control, the open

degree of valve is adjusted to the stop

position.