Toshiba CARRIER RAS-15LKV-UL User Manual

Page 31

Advertising
background image

– 31 –

Item

2. Indoor fan

motor control

Operation flow and applicable data, etc.

<In heating operation>

Description

[In starting and in stability]

(Fig. 3)

(Fig. 4)

(Fig. 5)

Cold draft preventive control

(Fig. 6)

L

L+

M

M+

H

W8

(L + M) / 2

WA

(M + H) / 2

WE

Indication

Fan speed

Fan speed setup

HEAT ON

AUTO

YES

NO

MANUAL

TC

108ºF (42˚C)

Min air flow rate control

Tc ºF (ºC)

Limited to Min WD tap

* Fan speed =

(TC –

– W8) + W8

No limit

*

Fan speed

AUTO

Basic fan control

* No limitation while fan speed MANUAL mode is in stability.
* A: When Tsc

≥ 75°F (24°C), A is 75°F (24°C), and

Tsc: Set value

b

c

d

e

f

g

L+ (W9)

M+ (WD)

*1

*2

*3

H (WE)

H (WE)

Linear-approximate
H and SUL with Tc.

SUL (W2)

Stop

115 (46) 115 (46)

Tc

93 (34)

*A+4

*A+4

*A+4

*A-4

*A-4

*A-4

Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting

*1: Fan speed = [(M+)

− (

L+)] x 1 4 + L+

*2: Fan speed = [(M+)

− (

L+)] x 2 4 + L+

*3: Fan speed = [(M+)

− (

L+)] x 3 4 + L+

(Calculated with linear approximation from M+ and L+)

Ta °F [°C]

TSC

-1.0 (-0.5)

-2.0 (-1.0)

-2.7 (-1.5)

-3.5 (-2.0)

-4.5 (-2.5)

-9.0 (-5.0)

-10.0 (-5.5)

°F (°C)

113 (45) 113 (45) 91 (33)

91 (33) 91 (33)

70 (21)

90 (32) 90 (32) 68 (20)

when Tsc < 75°F (24°C), A is Tsc

FAN AUTO

FAN Manual

In starting

• Until 12 minutes passed after operation start
• When 12 to 25 minutes passed after operation

start and room temp. is 5.4°F (3°C) or lower than set temp.

• Room temp. < Set temp. -7.2°F (– 4°C)

In stability

• When 12 to 25 minutes passed after operation start

and room temp. is higher than [set temp. -5.4ºF (–3°C)]

• When 25 minutes or more passed after operation start

• Room temp.

Set temp. -6.3°F (–3.5°C)

FILE NO. SVM-10020

106 (41)

1) When setting the fan speed to L,

L+, M, M+ or H on the remote
controller, the operation is per-
formed with the constant speed
shown in Fig. 3 and Table 1.

2) When setting the fan speed to

AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 5 according to the set
temperature and room temperature.

3) Min air flow rate is controlled by

temperature of the indoor heat
exchanger (Tc) as shown in Fig. 4

for prevent high temperature of heat
exchanger.

4) Cold draft prevention, the fan speed

is controlled by temperature of the

5) In order to prevent Cold draft when

compressor stop during heating
operation. Then louver will move to
upper position and fan speed will

reduce or off.

126 (52)
124 (51)

108 (42)
1

indoor heat exchanger (Tc) as shown
in Fig. 6 for keep warm temperature
of air flow.