Gas side
Ø1/2 in. (Ø12.70 mm)

37 to 46 lbf.ft
(50 to 62 N·m)

Gas side
Ø3/8 in. (Ø9.52 mm)

24 to 31 lbf.ft
(33 to 42 N·m)

Liquid side
Ø1/4 in. (Ø6.35 mm)

10 to 13 lbf.ft
(14 to 18 N·m)

Service port

10 to 13 lbf.ft
(14 to 18 N·m)

Hexagon wrench
is required.

3/16

in.

(4

mm

KEEP IMPORTANT 5 POINTS FOR PIPING

WORK.

(1) Take away dust and moisture (inside of the
connecting pipes).
(2) Tighten the connections (between pipes and
unit).
(3) Evacuate the air in the connecting pipes using
a VACUUM PUMP.
(4) Check gas leak (connected points).
(5) Be sure to fully open the packed valves before
operation.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equip-
ment damage or improper operation.
Never use the system compressor as a vacuum
pump.

CAUTION

FILE NO. SVM-10020

10-5-2. Packed valve handling precautions

Open the valve stem until it touches the stopper.

Once it is in contact with the stopper, refrain form

applying any more force than is necessary.

Securely tighten the valve stem cap with torque

in the following table:

Fig. 10-5-2

10-6. SYSTEM REQUIREMENTS

Minimum refrigerant line length between the outdoor
unit and indoor unit is

6.6ft. (2m).

Maximum pipe lengths

Allowable Pipe length T

(ft (m))

Height difference

(ft (m))

66 (20)

33 (10)

Refrigerant pipe sizes

H

T

Liquid side

Gas side

Outer

Diameter

In. (mm)

Thickness

In. (mm)

Outer diameter

In. (mm)

Thickness

In. (mm)

(09, 12LKV) (15, 17, 22LKV)

Ш1/4 (6.35)

0.03 (0.8)

Ш3/8 (9.52)

Ш1/2 (12.70)

0.03 (0.8)

Both lines need to be insulated. Use a minimum
5/16 in (8mm) wall thickness.

10-6-1. Piping (Field supplied)

(Indoor

− Outdoor H)

Insulation

– 63 –