(2) Characteristics required for flux

• Activated temperature of flux coincides with

the brazing temperature.

• Due to a wide effective temperature range, flux

is hard to carbonize.

• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and

brazing filler is minimum.

• It excels in coating performance and is

harmless to the human body.

As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.

(3) Types of flux

• Noncorrosive flux

Generally, it is a compound of borax and boric
acid.
It is effective in case where the brazing
temperature is higher than 800°C.

• Activated flux

Most of fluxes generally used for silver brazing
are this type.
It features an increased oxide film removing
capability due to the addition of compounds
such as potassium fluoride, potassium chlo-
ride and sodium fluoride to the borax-boric
acid compound.

(4) Piping materials for brazing and used braz-

ing filler/flux

2-5-3. Brazing

As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.

In order to prevent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.

Never use gas other than Nitrogen gas.

(1) Brazing method to prevent oxidation



Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.

‚

Use a copper pipe to direct the piping
material, and attach a flow-meter to the
cylinder.

ƒ

Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.

„

When the Nitrogen gas is flowing, be sure to
keep the piping end open.

…

Adjust the flow rate of Nitrogen gas so that it
is lower than 0,05 m

3

/Hr or 0,02 MPa (0,2kgf/

cm

2

) by means of the reducing valve.

†

After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools
down to a certain extent (temperature at
which pipes are touchable with hands).

‡

Remove the flux completely after brazing.

Fig. 2-5-1 Prevention of oxidation during brazing

Piping

material

Copper - Copper

Copper - Iron

Iron - Iron

Used brazing

Used

filler

flux

Phosphor copper

Do not use

Silver

Paste flux

Silver

Vapor flux



Do not enter flux into the refrigeration cycle.

‚

When chlorine contained in the flux remains
within the pipe, the lubricating oil deterio-
rates. Therefore, use a flux which does not
contain chlorine.

ƒ

When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange water).

„

Remove the flux after brazing.

Nitrogen gas

cylinder

Pipe

Flow meter

M

Stop valve

From Nitrogen cylinder

Nitrogen
gas

Rubber plug