– 47 –

YES

NO

Replace
the board.

Turn off the
power supply.

Does the fan

stop in no operating

status?

Control board is defective.

Replace the board.

Start the operation
with low fan setting
in cool operation.

Does the fan rotate?

Change the setting of
cooling to high fan.

Does the fan speed

become higher?

Operation
stops

Normal

Is the DC 35V

measured between

1

(red lead wire) and

2

(black lead wire)

of the motor connector

(CN10) ?

Turn off the power supply.

Does the cross

flow fan rotate

normally?

Repair the
bearing of the
cross flow fan.

Turn on the power supply.

Is the rotation signal

(DC+5V 0V) output between

4 (blue lead wire) and

2

(black

lead wire) of the motor connector

(CN10) when rotating the cross

flow fan by hand in no operating

status ? (2 pulses/one turn)

Replace the
control board.

Turn off the power supply,
and turn it on after
removing the motor from
the board.

Is the voltage of

DC35V measured

between 1 and 2 GND of

the motor connector

(CN10) ?

Replace the
fan motor.

Turn on the
power supply.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

Item by symptom

Operation

Check Item

Considerable main cause

Measures

(3) Only the indoor fan does not operate