Toshiba RAS-10YKV-E User Manual

Page 50

Advertising
background image

– 50 –

Refer to the chart in 10-6.

Gas leak

P.M.V. is defective.

Miswiring of connecting wires of indoor/outdoor units

Clogging of pipe and coming-off of TC sensor

Gas circulation amount is down.

Measure gas pressure.

Gas shortage

Gas leak

Pipe clogging

Thermo. operation of compressor

Red

White

Terminal block

S5277G

Tester

3

2

1

Terminal block at indoor side

S5277G or equivalent (G or J type)
(Diode with rated voltage of 400V
or more is acceptable.)

To item of Compressor does not operate.

10-5-2. Wiring Failure (Interconnecting and Serial Signal Wire)

(1) Outdoor unit does not operate

1) Is the voltage between

R

and

S

of the indoor terminal block varied?

Confirm that transmission from indoor to outdoor is correctly performed based upon the following dia-
gram.

NOTE:

• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.

• Be sure to prepare a diode for judgment.

Normal time

: Voltage swings between DC15 and 60V.

Abnormal time : Voltage does not vary.

(2) Outdoor unit stops in a little while after operation started

<Check procedure> Select phenomena described below.

(1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to

restart the unit.

(2) If the unit stops once, it does not operate until the power will be turned on again.

(3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.

(Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)