Toshiba RAS-10YKV-E User Manual

Page 56

Advertising
background image

– 56 –

Checking procedure

Disconnect the connector and measure the resistance value with tester.
(Normal temp.)

To item of How to judge whether remote controller is good or bad of the
Judgment of trouble by symptom.

Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)

Since judgment of DC motor is difficult on the single motor, refer to 10-
5-1. (3).

No.

Part name

1

Room temp. (TA) sensor
Heat exchanger (TC) sensor

2

Remote controller

3

Louver motor
MP35EA7

4

Indoor fan motor

Position

Resistance value

1 to 4
1 to 6

130 ± 10

2 to 3
2 to 5

Temperature

10°C

20°C

25°C

30°C

40°C

Sensor

TA, TC (k

)

20,7

12,6

10,0

7,9

4,5

No.

Part name

1

Compressor
(Model : DA91A1F-44F)

2

Outdoor fan motor
(Model : ICF-140-40-7)

3

Compressor thermo. Bimetal
type (Model : PW - 2AL)

4

Outdoor temperature sensor
(TO), discharge temperature
sensor (TD), suction
temperature sensor (TS),
outdoor heat exchanger
temperature sensor (TE)

Checking procedure

Measure the resistance value of each winding by using the tester.

Measure the resistance value of winding by using the tester.

For details, refer to Section 10-9.

Check conduction by using the tester.

Disconnect the connector, and measure resistance value with the tester.
(Normal temperature)

TGa : Heat pump model only.

TO, TS, TE : Refer to the TA, TC characteristic table in Indoor (Refer to
Table 10-8-3, No. 1).

Temperature

10°C

20°C

30°C

40°C

50°C

Sensor

TD (k

)

105

64

41

27

18

Brown

Red

Orange

Yellow

Pink

Blue

6

5

4

3

2

1

Position

Resistance value

Red

- White

0,51 to 0,57

White - Black

0,51 to 0,57

Black - Red

0,51 to 0,57

Under 20°C

Position

Resistance value

Yellow- Pink

5 to 20 k

Red

White

Black

Red

1 Yellow

4 Pink

5 Gray

White

Black

10-8-3. Indoor Unit (Other Parts)

10-8-4. Outdoor Unit