Toshiba RAS-10YKV-E User Manual

Page 67

Advertising
background image

– 67 –

No.

Part name

11

Replacement
of temperature
sensor for
servicing only

Common service
parts of sensor
TO, TS, TE, TD

These are parts
for servicing
sensors.

Please check
that the accesso-
ries shown in the
right table are
packed.

Remarks

Procedure

1) Cut the sensor 100 mm longer than old one.
2) Cut the protective tube after pulling out it

(200 mm).

3) Move the protective tube toward the thermal

sensor side and tear the tip of lead wire in
two then strip the covering part.

4) Pass the stripped part through the thermal

constringent tube.

5) Cut the old sensor 100 mm length on the

connector side, and recycle that connector.

6) Tear the lead wire in two on the connector

side and strip the covering part.

7) Twist the leads on the connector and sensor

sides, and solder them.

8) Move the thermal constringent tubes toward

the soldered parts and heat them with the
dryer and constring them.

9) Wind the attached color tape round the both

terminals of the protective tube when colored
protective tube is used.

10)Fix the sensor again.

NOTES :
1) Store the joint part of the sensor and the

connector in the electric parts box.

2) Never joint them near the thermal sensor

part. Otherwise it would cause insulation
inferiority because of dew drops.

3) When replacing the sensor using the colored

protective tube, wind the color tape matching
the color of that tube.

Parts name

Q'ty

Remarks

1

Sensor

1

Length : 3m

2

Sensor Spring (A)

1

For spare

3

Sensor Spring (B)

1

For spare

4

Thermal constringent tube

3

Including one spare

5

Color tape

1

9 colors

6

Terminal

3

Cutting here

Cutting here

Cutting here

Soldered part

Dryer

Winding the color tape

100

200

Connector

Thermal

sensor part

Thermal

constringent tube

70

15

100

70

15