Block distinction

Operation of diagnosis function

Check

code

Block

Check

code

Cause of operation

Air

conditioner

status

Remarks

Judgment and action

Inverter over-current
protective circuit
operates. (Short time)

All off

Displayed when
error is detected.

Even if trying operation again, all
operations stop immediately. : Replace
P.C. board.

Position-detect circuit
error or short-circuit
between windings of
compressor

All off

Displayed when
error is detected.

1. Even if connecting lead wire of

compressor is removed, position-
detect circuit error occurred. :
Replace P.C. board.

2. Measure resistance between wires

of compressor, and perform short-
circuit. : Replace compressor.

Current-detect circuit
error

All off

Displayed when
error is detected.

Even if trying operation again, all
operations stop immediately. :
Replace P.C. board.

Being out of place,
disconnection or short-
circuit of outdoor temp.
sensor

All off

Displayed when
error is detected.

1. Check outdoor temp. sensors

(TE, TS).

2. Check P.C. board.

Disconnection or short-
circuit of discharge temp.
sensor

All off

Displayed when
error is detected.

1. Check discharge temp. sensor (TD).
2. Check P.C. board

Outdoor
P.C. board

Outdoor fan drive system
error

All off

Displayed when
error is detected.

Position-detect error, over-current
protective operation of outdoor fan
drive system, fan lock, etc. :
Replace P.C. board or fan motor.

Not
displayed

Outdoor heat exchanger
temp. sensor error

Operation
continues

——

1. Check outdoor heat exchanger temp.

sensor (TE).

2. Check P.C. board.

Outdoor
P.C. board

Compressor drive output
error, Compressor error
(lock, missing, etc.),
Break down

All off

Displayed when
error is detected.

When 20 seconds passed after start-
up, position-detect circuit error
occurred. : Replace compressor.

Return serial signal has
been sent when
operation started, but it
is not sent from halfway.
(1) Compressor thermo.

operation
Gas shortage
Gas leak

(2) Instantaneous power

failure

Operation
continues

Flashes when
trouble is detected
on Return serial
signal, and normal
status when signal
is reset.

1. Repeat Start and Stop with interval

of approx. 10 to 40 minutes. (Code is
not displayed during operation.)
Supply gas. (Check also gas leak).

2. Unit operates normally during check.

If Return serial signal does not stop
between indoor terminal block 2 and
3, replace inverter P.C. board.
If signal stops between indoor
terminal block 2 and 3, replace
indoor P.C. board.

Compressor does not
rotate.
(Current protective
circuit does not operate
when a specified time
passed after compressor
had been activated.)

All off

Displayed when
error is detected.

1. Trouble on compressor
2. Trouble on wiring of compressor

(Missed phase)

Discharge temp.
exceeded 117°C

All off

Displayed when
error is detected.

1. Check dischage temp. sensor (TD).
2. Degassing
3. Trouble on P.M.V.

Break down of
compressor

All off

Displayed when
error is detected.

1. Check power voltage.

(220–30–40 V+10%)

2. Overload operation of refrigeration

cycle
Check installation condition
(Short-circuit of outdoor diffuser).

Others
(including
compressor)

Four-way valve inverse
error
(TC sensor value
lowered during heating
operation.)

Operation
continues

——

1. Check four-valve operation.