7. how to diagnose trouble in outdoor unit – Toshiba RAS-10YKV-E User Manual

Page 52

Advertising
background image

– 52 –

Diagnosis/Process flowchart

Item

Preparation

Check

Check

Operation

Measurement

Check

Stop

Check

Measurement

Contents

Turn “OFF” the power breaker,
and remove 3P connector
which connects inverter and
compressor.

• Check whether 25A fuse on

the control board assembly
is blown or not. (F01)

Check whether 15A fuse on
the control board assembly
is blown or not. (F03)

• 15A fuse (F03) on the

control board is provided for
power factor improvement
control circuit. The operation
continues even if fuse is
blown.

Turn on power breaker, and
operate the air conditioner in
COOL mode by short-circuit of
the timer.
Measure terminal voltage of
the electrolytic capacity.

500µF:400WV x 3

After operation, turn off the
power breaker after 2 minutes
20 seconds passed, and
discharge the electrolytic
capacity by soldering iron.
Check voltage between motor
phases.

• Is not winding between

Q

-

R

,

R

-

S

, or

Q

-

S

opened

or short-circuited?

• Is not frame grounded with

Q

,

R

, or

S

?

Summary

If fuse was blown, be sure to
check the electrolytic
capacitor and diode block.
(DB01)

• Connect discharge

resistance (approx.
100

40W) or soldering

iron (plug) between +, –
terminals of the electro-
lytic capacitor (500µF) of
C14 (with printed CAU-
TION HIGH VOLTAGE) on
P.C. board.

If 15A fuse is blown,
discharge both edges of
the electrolytic capacitor
with soldering iron.

OK if 500µF

DC280 to 320V

Remove CN300 while
pushing the part indicated
by an arrow because CN01
is a connector with lock.

Resistance between

phases should be approx. 55
to 77

Should be 10M

or more.

Replace
outdoor
fan motor.

Remove
connector of
compressor.

NG

NG

NG

NG

NO

NO

OK

OK

OK

OK

YES

YES

Check 25A fuse

(Part No.F01).

Does outdoor

fan rotate?

Replace fuse.

Check

electrolytic

capacitor, diode

block (DB01),

etc.

Check

electrolytic

capacitor, diode

(DB01),

etc.

Replace control
board assembly.

Remove connector

CN300 of outdoor fan

motor, and using a

tester, check resistance

value between every

phases at motor side.

Check

15A fuse

(Part No.F03).

Check

terminal voltage

of electrolytic

capacitor.

Does LED on control
board flash or go on?

C

B

A

Discharging position
(Discharging period
10 seconds or more)

Plug of
soldering
iron

10-7. How to Diagnose Trouble in Outdoor Unit

10-7-1. Summarized Inner Diagnosis of Inverter Assembly