8. OPERATION DESCRIPTION

8-1. Outline of Air Conditioner Control

This air conditioner is a capacity-variable type air
conditioner, which uses DC motor for the indoor fan
motor and the outdoor fan motor. And the capacity-
proportional control compressor which can change
the motor speed in the range from 13 to 120 rps is
mounted. The DC motor drive circuit is mounted to
the indoor unit. The compressor and the inverter to
control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the
indoor unit controller.

The indoor unit controller drives the indoor fan motor
based upon command sent from the remote control-
ler, and transfers the operation command to the
outdoor unit controller.

The outdoor unit controller receives operation
command from the indoor unit side, and controls the
outdoor fan and the pulse modulating valve.
Besides, detecting revolution position of the com-
pressor motor, the outdoor unit controller controls
speed of the compressor motor by controlling output
voltage of the inverter and switching timing of the
supply power (current transfer timing) so that motors
drive according to the operation command. And
then, the outdoor unit controller transfers reversely
the operating status information of the outdoor unit
to control the indoor unit controller.

As the compressor adopts four-pole
brushless DC motor, the frequency of the
supply power from inverter to compressor is
two-times cycles of the actual number of
revolution.

(1) Role of indoor unit controller

The indoor unit controller judges the operation
commands from the remote controller and
assumes the following functions.

• Judgment of suction air temperature of the

indoor heat exchanger by using the indoor
temp. sensor.

• Temperature setting of the indoor heat ex-

changer by using heat exchanger sensor
(Prevent-freezing control)

• Louver motor control

• Indoor fan motor operation control

• LED display control

• Transferring of operation command signal

(Serial signal) to the outdoor unit

• Reception of information of operation status

(Serial signal including outside temp. data) to
the outdoor unit and judgment/display of error

(2) Role of outdoor unit controller

Receiving the operation command signal (Serial
signal) from the indoor controller, the outdoor
unit performs its role.

• Compressor operation

control

• Operation control of

outdoor fan motor

• P.M.V. control

Operations followed
to judgment of serial
signal from indoor
side.

• Detection of inverter input current and current

release operation

• Over-current detection and prevention opera-

tion to transistor module (Compressor stop
function)

• Compressor and outdoor fan stop function

when serial signal is off (when the serial signal
does not reach the board assembly of outdoor
control by trouble of the signal system)

• Transferring of operation information (Serial

signal) from outdoor unit to indoor unit

• Detection of outdoor temperature and opera-

tion revolution control

• Defrost control in heating operation (Temp.

measurement by outdoor heat exchanger and
control for four-way valve and outdoor fan)