Xylem HYDROVAR Smart User Manual

Page 12

Advertising
background image

12

3.4

Pressure

transducer

PA-22S

(4-20mA)

The sensor of this transmitter is a piezoresistive silicon pressure sensor, mounted on a tape
(TAP) freely floating in an oil chamber. The pressure is transferred to the sensor by a
separate steel diaphragm in the oil chamber.

Specification

Range (FS):

10 bar

16 bar 25 bar 40 bar

Max. pressure – P

max

:

20 bar

30 bar 50 bar 80 bar

Class of protection IP 67
Output signal:

4...20 mA; 2-wire

Supply:

8 – 28 VDC

Operating temperature: -10...80°C compensated (max. –40...135 °C)
Storage temperature:

-40...135°C

Cable length:

2 m (screen)

Material:

Body: 1.4435
Diaphragm: 1.4435
Thread: G ¼“

Measures in mm



Note: To guarantee the protection class IP67, the rubber gasket has to be
mounted between the pressure transducer and the plug!

4

Control Terminals and Display unit

All externally used cables must to be shielded. Do not connect the ground of the electronic
components to other potentials (all electronic ground and GND of the RS 485-interface are
connected together internally).

Electrical connection:
White = Analogue output signal (+ Out) (1)
(2) not used

Brown = Supply voltage (+ VCC) (3)

Gasket Viton

®

Pressure transmitter

Gasket

Plug / cable