An error indication is given over terminal X2/1, X2/2 and X2/3 (changeover contact).
If no Error is active, the relay is switched on and terminals X2/2 and X2/3 are closed.

Attention If "AUTO - START ON" and "ERROR-RESET – ON" are programmed, the unit

can start again automatically after a power failure.

8.6

Additional Error signals:

ERROR 1

:

EEPROM-ERROR (corresponding data block malfunction)

ERROR 2

:

Security error / Software protection error

ERROR 4

:

Display unit / Push buttons error (e.g.: jammed key)

ERROR 5

:

EPROM-error

ERROR 6

:

Program error: Watchdog

error

ERROR 7

:

Program error:

Processor pulse error

ERROR 8

:

Program error:

invalid processor command

These ERROR signals can be reset by cutting off the power supply or pressing all three
buttons (П,Р and ¾) together for about 5 seconds.
If the error signal should appear again, contact customer service and provide a detailed
description of the error.

9

RS 485 - Interface

Standardised Bus-Interface for communication between the inverters (Hydrovar-Smart and/or
Hydrovar Drive heads) and/or an overruling external control system.

The data protocol complies with ISO 1745 for RS 485 interfaces and contains the following
configurations:

Transfer rate : 9600 Baud (1 Start bit, 8 Data, 1 Stop bit)

An interface inverter RS 232/RS 485 is necessary in case communication with a V24 interface
of a PC or another external control system is wanted.

All parameters can be approached via the standard interface. The inline structure of the
Hydrovar-Smart Drive head can be obtained upon request.

For further information see:

serial data transmission – RS485

HYDROVAR-Smart – Protocol 120