7.10 Operation at the minimum frequency

CONFIG FMIN

f => fmin

If you have selected „f->0“ the frequency will go

down to the selected minimum frequency.

Then the inverter will keep running for the selected stop-delay time and after this time the
Hydrovar-Smart will stop automatically.

If the selection is „f->f

min

“ you can not run the pump below the set minimum frequency. In

the controller, actuator and multi controller mode the pump will never run below the set

minimum frequency (the pump will only stop with an external on/off-(terminals X1/4 and
X1/5) or in case of a failure.

Press ¾ on the Hydrovar-Smart to change to

7.11 Delay time for shut off at minimum frequency

STOP-DELAY FMIN

5 s

After running the pump for this selected time at
minimum frequency, the pump will stop, if parameter

CONFIG. FMIN is set to f ⇒ 0
Adjustable between 0 and 100s.

NOTICE!
Problems with shut off of the pump at 0 demand (too small or no pressure tank) can be
solved by using these settings!
Additional function: selectable delay time to start a full speed pump in case of “Simple
Multicontroller” mode.

Press ¾ on the Hydrovar-Smart to change to

7.12 Sensor – Adjust

SENSOR_ADJUST?

Out of range

Zero point adjustment of the transmitter
Depressurise the system and press buttons П + Р

simultaneously. After a successive adjustment, "adjusted" appears on the display.
If “out of range” is shown on the display, no adjustment is possible

Press ¾ on the Hydrovar-Smart to change to

7.13 Sensor - Curve

SENSOR-CURVE

Linear

Function of the input signal (4...20mA) of the
Hydrovar to the actual measured value.

Application:

linear: Pressure control, differential pressure control, level, temperature and flow control
(inductive or mechanical).
quadratic: Flow control by using an orifice plate together with a differential pressure
transmitter.

Press ¾ on the Hydrovar-Smart to change to