Xylem HYDROVAR Smart User Manual

Page 21

Advertising
background image

21

7.3 Ramp Hysteresis

RAMP HYSTERESIS

80%

Level, where the fast ramps are changing to the slow

ramps

Possible setting: between 0%..100% of the window


Press ¾ on the Hydrovar-Smart to change to

7.4 Ramp 1: Fast running up time:

Time setting at Ramp 1, 2, 3, or 4 will influence the control of the pump and

MUST NOT BE CHANGED at normal operation. Possible setting of each ramp
0,05 - 1000 sec.

Please take care, that the ramp times of the connected VFD are every time faster than the
settings of the ramps 1-4 of the HYDROVAR-Smart!
The fast ramp times 1 and 2 are determined by the power of the connected drive.

(Standard settings = 4-15s, depending on the power)

RAMP 1

4.0 Sec

Excessively fast running up time may overload the
inverter in the starting moment.
Excessively slow running up time may cause a break

down of the outgoing pressure during operation.

Press ¾ on the Hydrovar-Smart to change to

7.5 Ramp 2: Fast running down time:

RAMP 2

4.0 Sec

Excessively fast running down time tends to cause
oscillation or hunting or can cause an error

(OVERVOLTAGE) during ramp down of the pump.
Excessively slow running down time tends to generate over pressure.


Press ¾ on the Hydrovar-Smart to change to

7.6 Ramp 3: Slow running up time:

The following ramps 3 and 4 determine the speed of the internal Hydrovar-Smart controller
and depend on the system, which should be controlled.

RAMP 3

70 Sec

A too slow running up time can cause a break of the
outgoing pressure during variation of the demand.
A too fast running up time may lead to oscillation
and/or overload of the inverter.


Press ¾ on the Hydrovar-Smart to change to