6parameters of the main menu – Xylem HYDROVAR Smart User Manual

Page 16

Advertising
background image

16

6

Parameters of the main menu

After connection of the Hydrovar-Smart unit to the power supply the following displays
become visible.

SW-Ver: HV00-001
Date: xxxx

The current software version with the date of
programming is displayed for about 3s.

The following two displays are depending on the selected mode:

a) Active MODE = Controller:

1.

XX.X BAR

This window is mentioned several times in the

Operating Instructions as 1

st

display at Mode Controller

Continue by pressing the ¾-button

2.

REQUIRED VALUE 1

X.XX BAR

Set the desired set pressure with either Ï or Ð and
then briefly press the ¾-button.

If several pumps are connected via the RS-485 interface, one pump must be ready for
operation when the set pressure is changed, otherwise the set value will not be accepted
by the follow-up pumps. Afterwards the new required pressure has to be saved in all

pumps.

If you want to change to Required Value 2 you have to close the external contact,
connected to X1/10-X1/14.

After closing this contact, the display changes from Required value 1 to

2.1

REQUIRED VALUE 2

ADC-X XX.X BAR

In this window, there is shown the condition of
the second Required value.

ADC-X: This parameter shows the source of the external or internal value.
XX.X Bar: shows the actual value of the Required Value 2.

Continue by pressing the ¾-button (to point 3)