7.23 Compensation Frequency


Control according to a system curve (increase of the set pressure, depending upon the

flow rate or speed).

FREQU. – LIFTING

30.0 Hz

Adjustable between 6 Hz and the set MAXIMUM
FREQUENCY, this setting states at which frequency the

set pressure should be increased. That is the speed, where the pump works at the set

pressure and at a flow rate=0 (can be read in the JOG MODE).

Press ¾ on the Hydrovar-Smart to change to

7.24 Lift-Intensity

LIFT – AMOUNT

0.0 %

Adjustable from 0% to 99,9%; this value states how

much the set value should be increased, when the
pump is running at maximum speed (=maximum

flow).

1. Setting of the required pressure (see: Inverter main menu)
2. Enter frequency for demand = 0 and set pressure = Actual Value

(see: Jog Mode ) ⇒ FREQU. LIFTING

3. Set desired lift at maximum speed, in % of required pressure.


Figure:

Lift-Intensity