7

Settings in the Secondary Menu


Important! Before entering the secondary menu, these instructions
have to be read carefully to prevent incorrect settings which could cause

malfunction.

Secondary Menu:

INVERTER STOP

ON -> START

Stop motor by pressing Ð (OFF)

PASSWORD

0000

Press ¾ for 3 seconds to change to

PASSWORD

0066

Set ‘Password 0066’ by pressing Ï

Note: The password must be entered at each entry!

J O G – MODE

0.0Hz X.XX Bar

Confirm by pressing ¾ and the first window of the sub

menu is shown

In the following paragraphs all possible settings are listed (in the display, there
is shown the European default setting).

7.1 JOG-MODE

Display and Manual Operation Mode

J O G – MODE

0.0Hz X.XX Bar

Actual outgoing frequency and actual analogue input
are shown. By pressing Ï or Ð in this menu, the

internal controller of the Hydrovar-Smart will be shut off and the inverter changes to
manual mode. With the buttons Ï and Ð you can set any constant speed.
Setting of 0,0 Hz stops the inverter. If the JOG-MODE is left at a frequency higher than 0,0
Hz the inverter will continue its normal automatic operation.

Press ¾ on the Hydrovar-Smart to change to

7.2 Window - %

WINDOW

5%

This value indicates the max. variation of the outgoing
pressure.

Possible setting: between 0% - 100% of required value.

Press ¾ on the Hydrovar-Smart to change to

Advertising