Xylem HYDROVAR Smart User Manual

Page 13

Advertising
background image

13

For external on/off switches, (terminals X1/4 – X1/5) contacts, which are suitable for

switching low voltages <10 VDC, are necessary.
If unshielded control cables are used, signal interference may occur and interfere
with the function of the controller.

Terminals:

X1/ 1 GND

2 Actual value input 4...20mA, 50 Ohm internal load resistance

3 Power supply for external transducer; 15VDC, max. 100mA

4

GND

5 5 VDC for external on/off (release); Ri=10kOhm,

(gold plated contact necessary!)

6

GND

7 5 VDC for external low water protection; Ri=10kOhm,

(e.g. incoming pressure switch or water level switch)

8 Thermal switch or PTC (in motor terminal box)

9 Thermal switch or PTC

10

GND

11 Analogue output 2; 0...10 VDC (see chapter 7.25)
12 Current signal input 4...20mA
13 Voltage signal input 0...10V or 2...10V

14 Digital input for activating of 2

nd

required value

Terminal:

X2/ 1 Fault signal relay

NC

max. 250VAC

1A

free of inductivity

(for dry

2 Fault signal relay

CC

max. 250VAC

1A

free of inductivity

Contacts)

3 Fault signal relay

NO

max. 250VAC

1A

free of inductivity

4

Pump

operation

signal relay

NC max.

250VAC

1A

free of inductivity

5

Pump

operation

signal relay

CC max.

250VAC

1A

free of inductivity

6

Pump

operation

signal relay

NO max.

250VAC

1A

free of inductivity

!! Fault relay (X2/2 - X2/3) is closed, when there is no error!!

Terminal:

X3 Display

Terminal: X5-6/ 1 RS 485

SIO -

LOW

2 RS 485

SIO +

HIGH

3 RS 485

GND

4 RS 485

+ 5 VDC

max. 20mA out

For supply of external interface converter

Terminal:

X8 RS 485

Terminal: X9/ 1 24 VAC or DC

Supply Voltage

2 24 VAC or GND

Supply Voltage

3 Error relay of the connected VFD
4 Error relay of the connected VFD
5 Analogue output for the speed signal of the VFD (0-10V DC)
6 GND