Xylem HYDROVAR Smart User Manual

Page 25

Advertising
background image

25

If MANUAL CONTROL is selected, the parameter REQUIRED VALUE will change to MANUAL

CONTROL in the main menu, where the actual frequency and the actual value is displayed
(according to the JOG-MODE in the submenu).
Now the frequency can be changed with the Ï and Ð buttons, and the speed of the pump

will change with the fasten ramps. After selecting the right frequency, it can be saved with

the standard SAVE.
After a supply failure, the pump will then run with this selected frequency (depending on

the parameter AUTO-START).
The frequency can be changed between the set minimum and maximum frequency.


In the 1

st

display, there is shown the actual frequency.

NOTE:

CONFIG. FMIN will not work in this mode.


Attention Driving the pump in a not allowed speed range can damage the motor or the

inverter!

Press ¾ on the Hydrovar-Smart to change to

7.16 Control Response

REGULATION MODE

Normal

Normal: Speed is increased with falling actual value
signals. (e.g.: Control at constant output pressure).
Inverse: Speed is reduced with falling actual value
signal, (e.g.: Control at constant suction pressure or at
constant level).

Press ¾ on the Hydrovar-Smart to change to

7.17 Start Value

START VALUE

disabled

This parameter gives you the start value after pump

stop in percentage of the required value (adjustable
between disabled and sensor range).

Example:

required value:

5,0 bar

start value:

2,5 bar

If the pump system have reached the required pressure from 5.0 Bar and there is no more
consumption, the Hydrovar-Smart shuts off the pump. When the consumption increases
and the pressure goes down the pump will normally start. If you have selected the START
VALUE at 2,5 bar the pump will start again at this selected pressure.

Press ¾ on the Hydrovar-Smart to change to